JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Startup
The supply, exhaust and return fans 
have tie down bolts are installed at the 
factory to prevent movement in the fan 
assemblies during shipment. THESE 
HOLD  DOWN  BOLTS  MUST  BE 
REMOVED PRIOR TO OPERATION 
OF THE ABOVE FANS. There are 
eight bolts per assembly two at each 
comer of the fan skids, front and rear. 
The bolt locations are shown in Figure 
3-1. The bolt heads are red in color 
and a label identifies their location in 
the unit. 
13.  Verify proper belt tension of supply fan, exhaust 
fan or return fan (refer to Maintenance section of 
manual). Belts must be checked after 24 hours of 
initial operation.
 14.  Manually  rotate  condenser  fan  blades,  supply 
exhaust and return blower wheels and motors, to 
assure freedom of movement.
 15.  Verify proper condensate drain trap installation 
(refer to Figure 2-6). Fill traps with water prior to 
unit start-up.
 16.  If applicable, verify installation of air filters (refer 
to Installation section for size and quantity).
FIG. 3-1 – FAN HOLD DOWN BRACKETS
SUPPLY FAN ASSEMBLY
EXHAUST FAN ASSEMBLY
Fan Hold Down Brackets (4)
Fan Hold Down
Brackets (4)