York YRHBC User Manual

Page of 16
INSTALLATION
6
YORK INTERNATIONAL
FORM 115.20-NOM2 (105)
7
YORK INTERNATIONAL
INSTALLATION
FORM 115.20-NOM2 (105)
VALVE CLUSTER
2-Way Motorized Valve Assemblies
 1.  The motorized valve assembly should be attached to 
the supply header, which is the connection nearest 
the air outlet flange on the unit.
 2.   Prior to soldering the joints, operate all the hand 
valves to ensure that the handles will fully open and 
close without interference to other valves, ceiling, 
wall, plenum or other accessories.
 3.  All valves will operate at any angle with the excep-
tion of the motorized valve, which must be installed 
with the power head above horizontal. The actuator 
box requires a 3/4" clearance for removal.
3-Way Motorized Valve Assembly
 1.  The  3-way  valve  assemblies  will  mount  to  the 
coil in only one position. On four-pipe right hand 
systems, a "B" valve assembly is required for the 
chilled water connection and an "A" valve assembly 
is required for the hot water connection. On left 
hand systems, an "A" valve assembly is required 
for the chilled water connection and the hot water 
connection. (See figure 4.)
 2.   Prior to soldering the joints, operate all the hand 
valves to ensure that the handles will fully open and 
close without interference to other valves, ceiling, 
wall, plenum or other accessories.
 3.  All valves will operate at any angle with the excep-
tion of the motorized valve, which must be installed 
with the power head above horizontal. The actuator 
box requires a 3/4" clearance for removal.
FIG. 5 – 3 WAY MOTORIZED VALVE ASSEMBLY
00187VIP
FIG. 4 – 2 WAY MOTORIZED VALVE ASSEMBLY
00186VIP
DRAIN PIPING
Condensate drain lines must be installed with adequate 
slope away from the unit to assure positive drainage. 
YRHBC and YCHBC fan coil units require a minimum 
trap of 1-1/2 inches be provided in the drain line to 
assure proper drainage. YHBC, YPHBC, YHH, YPHH, 
YHYB, and YPHYB fan coil units may be located where 
the  return  air  space  is  large  enough  that  a  negative 
pressure is not present, however, a trapped condensate 
line is recommended to ensure proper drainage of unit in 
case a negative condition should occur (see Installation 
Drawings for locations and sizes).
The drain should always be connected or piped to an 
acceptable disposal point sloped away from the unit at 
least 1/8" per foot
LD04801
FIG. 6 – TYPICAL CONDENSATE PIPING
UNIT
PRIMARY
SECONDARY
YHBC
3/4 MPT
5/8 OD
YPHBC
3/4 MPT
3/4 MPT
YRHBC
3/4 MPT
3/4 MPT
YHH
3/4 MPT
7/8 OD
YPHH
3/4 MPT
7/8 OD
YHYB
3/4 MPT
3/4 MPT
YPHYB
3/4 MPT
3/4 MPT
TABLE 2 - DRAIN LINE SIZES