3
YORK INTERNATIONAL
INSTALLATION
FORM 115.20-NOM3 (1006)
RECEIVING
Material  in  this  shipment  has  been  inspected  at  the 
factory  and  released  to  the  transportation  agency  in 
good condition. When received, a visual inspection of 
all cartons should be made immediately. Any evidence 
of rough handling or apparent damage should be noted 
on the delivery receipt and the material inspected in the 
presence of the carrier's representative.
If damage is found, a claim should be 
filed against the carrier immediately.
STORAGE
If the equipment is not to be immediately installed, store 
it in a dry location with the motor protected against 
moisture, dust, corrosion and physical damage.
PREPARE WALL FOR MOUNTING
Depending  upon  building  construction,  provisions 
for mounting the unit must be made by the contractor 
according to architects; drawings.
Unit  must  not  be  operated  during 
building construction due to excessive 
airborne dust and debris. The units 
must not be operated under any cir-
cumstances  without  an  air  filter  in 
place.
It is recommended that all mounting 
holes be used for proper installation.
YVS / YVF UNIT STYLE (VERTICAL CABINET)
See Fig 7 for unit details and dimensions.
Mounting  location  must  allow  enough  clearance  to 
permit the removal of screws that secure the cabinet 
panels.  After selecting the location for the unit, remove 
the front panel. The front panel must be removed on 
the YVS or YVF unit to gain access to the coil, drain 
connections and electrical junction box.  To accomplish 
this:
 1.  Pull firmly on the lower cabinet door (each side)  
until the cabinet releases from its friction fastener.
 2.  Proceed to lift the door assembly straight up and 
off the cabinet frame.
YVC UNIT STYLE  ( VERTICAL CONCEALED)
See Fig 8 for unit details and dimensions.
Mounting  location  must  allow  enough  clearance  to 
permit the removal of screws that secure the cabinet 
panels.  After selecting the location for the unit:
 1.  Remove the front panel.
 2.  Position the unit in its permanent location, making 
sure it is level to insure proper drainage and opera-
tion, and secure the unit in place.
 3.  Secure the unit to the wall using the four, 1/2 inch 
holes provided (two on each end of the unit).
Access must be provided for servicing the unit. If this 
access is provided by a removable panel, ample space 
must be allowed for access to electrical and plumbing 
controls. 
YWC UNIT STYLE (RECESSED WALL)
See Fig 9 for unit details and dimensions.
Mounting  location  must  allow  enough  clearance  to 
permit the removal of all mechanical parts within the 
unit.
 1.  Frame the unit as required so the front panel of the 
wall unit will be flush with the drywall surface when 
installed.
 2.  Frame around the perimeter of the unit as required 
for securing the drywall.  See Table 1 below for 
drywall openings.
MODEL NUMBER
DRYWALL CUTOUT DIM 
HT x WD
3YWC
28 x 42
4YWC
28 x 50
6YWC
28 x 58
8YWC
28 x 66
10YWC
28 x 74
12YWC
28 x 82
TABLE 1 – DRYWALL OPENINGS