York DM 078 User Manual

Page of 48
246645-YTG-C-0708
Johnson Controls Unitary Products
13
TABLE 5:  COOLING CAPACITY DM078 (6-1/2 TON) UNIT 
Air On
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Temperature of Air on Condenser Coil 95°F
CFM
WB
(°F)
Tot.
Cap.
*
(MBH)
Tot.
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Tot.
Cap.
*
(MBH)
Tot.
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1950
72 87
6.8
49
43
37
32
26
-
-
78
7.3
45
40
34
28
23
-
-
67 80
6.7
61
55
50
44
38
33
27
73
7.1
57
52
46
41
35
29
24
62 71
6.4
71
66
61
55
50
44
39
63
6.9
63
61
56
50
45
39
33
57 66
6.4
66
66
61
56
50
44
39
59
6.8
59
59
54
49
43
37
32
2275
72 91
6.9
54
47
41
34
28
-
-
82
7.4
50
44
37
31
24
-
-
67 83
6.7
67
61
54
47
41
34
28
76
7.2
64
57
51
44
38
31
24
62 74
6.5
74
72
66
60
53
47
40
66
6.9
66
65
61
55
48
42
35
57 69
6.5
69
69
67
60
54
47
40
62
6.9
62
62
60
53
46
40
33
2600
72 94
7.0
59
52
44
37
29
-
-
86
7.5
56
48
41
33
26
-
-
67 87
6.8
74
66
58
51
43
36
28
80
7.3
70
63
55
48
40
33
25
62 77
6.6
77
77
72
64
57
49
42
69
7.0
69
69
67
59
52
44
37
57 72
6.6
72
72
72
65
57
49
42
65
7.0
65
65
65
57
50
42
35
2925
72 95
7.0
63
55
46
37
29
-
-
85
7.5
60
51
43
34
25
-
-
67 88
6.8
78
70
61
52
44
35
26
79
7.3
74
66
58
49
40
32
23
62 77
6.6
77
77
75
66
58
49
40
69
7.1
69
69
67
59
50
42
33
57 73
6.6
73
73
73
64
56
47
38
64
7.0
64
64
64
56
47
39
30
3250
72 96
7.0
67
58
48
38
29
-
-
85
7.5
64
54
44
35
25
-
-
67 89
6.8
83
73
64
54
44
35
25
78
7.3
78
70
60
50
41
31
21
62 78
6.6
78
78
78
68
59
49
39
68
7.1
68
68
68
58
49
39
29
57 74
6.6
74
74
74
64
54
45
35
64
7.1
64
64
64
54
45
35
25
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
1950
72 73
7.8
43
37
31
26
20
-
-
67
8.3
40
35
29
23
18
-
-
67 66
7.5
54
48
43
37
32
26
21
58
7.9
51
45
40
34
29
23
17
62 64
7.4
61
57
52
46
41
35
30
66
7.9
59
54
48
42
37
31
26
57 54
7.3
54
54
48
43
37
32
26
48
7.8
48
48
43
37
31
26
20
2275
72 76
7.9
48
41
34
28
21
-
-
69
8.4
45
38
32
25
18
-
-
67 68
7.6
60
54
47
40
34
27
21
60
8.0
56
50
43
37
30
24
17
62 67
7.5
65
62
57
50
44
37
31
67
8.0
64
59
52
46
39
33
26
57 56
7.4
56
56
53
46
40
33
27
49
7.9
49
49
46
40
33
27
20
2600
72 78
8.0
53
45
38
30
22
-
-
71
8.4
49
42
34
27
19
-
-
67 71
7.7
66
59
51
44
36
28
21
61
8.1
61
55
47
39
32
24
17
62 69
7.5
69
67
62
54
47
39
31
69
8.0
69
64
57
49
42
34
26
57 58
7.5
58
58
58
50
42
35
27
50
7.9
50
50
50
43
35
28
20
2925
72 78
8.0
57
48
40
31
23
-
-
71
8.5
54
46
37
28
20
-
-
67 70
7.7
68
62
54
46
37
28
20
62
8.2
62
58
51
42
33
25
16
62 69
7.6
69
68
64
56
47
38
30
69
8.1
69
67
61
53
44
35
27
57 58
7.5
58
58
58
49
40
32
23
51
8.0
51
51
51
42
33
25
16
3250
72 78
8.1
61
52
42
32
23
-
-
71
8.6
59
49
40
30
20
-
-
67 70
7.8
70
66
57
48
38
28
19
62
8.3
62
62
55
45
35
25
16
62 69
7.6
69
69
67
57
48
38
28
70
8.2
70
70
66
56
46
37
27
57 57
7.6
57
57
57
48
38
28
19
51
8.1
51
51
51
41
31
22
12
Temperature of Air on Condenser Coil 125°F
1950
72 
62
8.8
38
32
27
21
15
-
-
67 
51
8.4
48
42
37
31
25
20
14
62 
67
8.4
57
50
44
39
33
27
22
57 
42
8.3
42
42
37
31
26
20
15
2275
72 
63
8.8
42
35
29
22
16
-
-
67 
52
8.4
52
46
40
33
27
20
13
62 
68
8.5
63
56
48
41
35
28
22
57 
43
8.3
43
43
40
33
27
20
14
2600
72 
63
8.9
46
39
31
23
16
-
-
67 
52
8.5
52
50
43
35
28
20
12
62 
69
8.5
69
62
52
44
37
29
21
57 
43
8.4
43
43
43
35
28
20
13
2925
72 
64
9.0
52
43
34
26
17
-
-
67 
53
8.6
53
53
47
39
30
21
13
62 
70
8.6
70
66
58
50
41
32
24
57 
44
8.5
44
44
44
35
26
18
9
3250
72 
65
9.1
57
47
38
28
18
-
-
67 
54
8.7
54
54
52
42
32
23
13
62 
71
8.8
71
71
65
55
45
36
26
57 
44
8.6
44
44
44
34
25
15
5
*
These capacities are gross ratings. For net 
capacity, deduct air blower motor, MBH = 3.415 
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air 
blower motor.
These ratings include condenser fan motors 
and the compressor motors but not the supply 
air blower motor.