York DM 078 User Manual

Page of 48
246645-YTG-C-0708
Johnson Controls Unitary Products
15
TABLE 7: COOLING CAPACITY DM102 (8-1/2 TON) UNIT
Air on Evap-
orator Coil
Temperature of Air on Condenser Coil
75°F
85°F
CFM
WB
(°F)
Total
Cap.
*
(MBH)
Total
† 
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
*
(MBH)
Total
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2550
72 123.8
7.4
68.9
61.6
54.3
47.1
39.8
-
-
114.8
8.0
65.3
58.0
50.8
43.5
36.2
-
-
67 112.4
7.3
85.2
78.0
70.7
63.4
56.2
48.9
41.6
104.3
7.9
81.9
74.6
67.3
60.1
52.8
45.5
38.3
62 106.9
7.1
106.9
95.5
88.1
80.8
73.5
66.3
59.0
96.4
7.7
96.4
90.7
83.5
76.2
68.9
61.6
54.4
57 99.3
7.1
99.3
98.9
91.5
84.2
76.9
69.7
62.4
93.2
7.7
93.2
92.9
85.7
78.4
71.1
63.9
56.6
2975
72 127.6
7.4
75.6
67.0
58.5
49.9
41.3
-
-
118.7
8.1
72.0
63.4
54.8
46.2
37.6
-
-
67 115.9
7.3
93.2
84.6
76.0
67.4
58.8
50.2
41.7
107.8
7.9
89.9
81.3
72.7
64.1
55.5
46.9
38.3
62 110.3
7.2
110.3 104.6
94.7
86.1
77.5
69.0
60.4
99.7
7.7
99.7
96.9
90.1
81.5
72.9
64.3
55.7
57 102.4
7.1
102.4 102.2
98.4
89.8
81.2
72.6
64.0
96.3
7.8
96.3
96.2
92.5
83.9
75.3
66.7
58.1
3400
72 131.5
7.5
82.4
72.5
62.6
52.6
42.7
-
-
122.6
8.2
78.7
68.7
58.8
48.9
39.0
-
-
67 119.4
7.4
101.2
91.3
81.3
71.4
61.5
51.6
41.7
111.3
8.0
97.9
88.0
78.0
68.1
58.2
48.3
38.4
62 113.7
7.2
113.7 113.7 101.4
91.5
81.5
71.6
61.7
103.0
7.8
103.0 103.0
96.7
86.8
76.9
67.0
57.1
57 105.5
7.2
105.5 105.5 105.3
95.4
85.5
75.5
65.6
99.5
7.8
99.5
99.5
99.3
89.4
79.5
69.5
59.6
3825
72 134.7
7.5
88.7
77.5
66.2
54.9
43.6
-
-
125.2
8.2
85.0
73.7
62.4
51.1
39.8
-
-
67 122.3
7.4
110.0
97.3
86.0
74.7
63.4
52.1
40.9
113.7
8.0
105.4
94.1
82.8
71.5
60.2
48.9
37.6
62 116.4
7.3
116.4 116.4 110.3
99.0
87.7
76.4
65.1
105.2
7.8
105.2 105.2 102.1
90.8
79.5
68.2
56.9
57 108.1
7.3
108.1 108.1 108.0
96.7
85.4
74.1
62.8
101.6
7.9
101.6 101.6 101.5
90.2
78.9
67.6
56.4
4250
72 137.9
7.6
95.1
82.4
69.8
57.1
44.4
-
-
127.8
8.3
91.3
78.7
66.0
53.3
40.7
-
-
67 125.3
7.5
118.8 103.4
90.7
78.0
65.4
52.7
40.0
116.1
8.1
112.9 100.2
87.6
74.9
62.2
49.6
36.9
62 119.2
7.3
119.2 119.2 119.2 106.5
93.8
81.2
68.5
107.4
7.9
107.4 107.4 107.4
94.8
82.1
69.4
56.8
57 110.7
7.3
110.7 110.7 110.7
98.0
85.3
72.6
60.0
103.8
7.9
103.8 103.8 103.8
91.1
78.4
65.8
53.1
95°F
105°F
2550
72 105.8
8.7
61.7
54.5
47.2
39.9
32.6
-
-
96.9
9.4
58.0
50.8
43.5
36.2
29.0
-
-
67 96.1
8.5
78.5
71.3
64.0
56.7
49.5
42.2
34.9
86.6
9.1
74.3
67.0
59.7
52.5
45.2
37.9
30.7
62 86.0
8.3
86.0
86.0
78.8
71.6
64.3
57.0
49.7
79.4
8.9
79.4
78.9
71.7
64.4
57.1
49.9
42.6
57 87.0
8.3
87.0
87.0
79.9
72.6
65.3
58.1
50.8
79.5
8.9
79.5
79.4
72.2
65.0
57.7
50.4
43.2
2975
72 109.7
8.8
68.3
59.7
51.1
42.5
34.0
-
-
100.5
9.4
64.6
56.0
47.4
38.8
30.2
-
-
67 99.7
8.5
86.6
78.0
69.4
60.8
52.2
43.6
35.0
89.8
9.1
81.5
73.7
65.1
56.5
47.9
39.3
30.7
62 89.1
8.3
89.1
89.1
85.4
76.8
68.3
59.7
51.1
82.3
9.0
82.3
82.1
78.1
69.5
60.9
52.3
43.7
57 90.2
8.4
90.2
90.2
86.6
78.0
69.4
60.8
52.2
82.5
9.0
82.5
82.4
78.7
70.1
61.5
52.9
44.3
3400
72 113.6
8.8
74.9
65.0
55.1
45.2
35.3
-
-
104.0
9.5
71.1
61.2
51.3
41.3
31.4
-
-
67 103.2
8.6
94.6
84.7
74.7
64.8
54.9
45.0
35.1
93.0
9.2
88.7
80.3
70.4
60.5
50.6
40.7
30.8
62 92.3
8.4
92.3
92.3
92.1
82.1
72.2
62.3
52.4
85.3
9.0
85.3
85.3
84.5
74.6
64.6
54.7
44.8
57 93.5
8.4
93.5
93.5
93.3
83.4
73.5
63.5
53.6
85.4
9.1
85.4
85.4
85.1
75.2
65.3
55.4
45.5
3825
72 115.7
8.9
81.2
70.0
58.7
47.4
36.1
-
-
105.6
9.5
77.4
66.1
54.8
43.5
32.2
-
-
67 105.1
8.6
100.8
90.9
79.6
68.3
57.0
45.7
34.4
94.5
9.2
92.3
85.7
75.3
64.0
52.7
41.4
30.1
62 94.0
8.4
94.0
94.0
93.9
82.6
71.3
60.0
48.7
86.6
9.1
86.6
86.6
86.2
74.9
63.6
52.3
41.0
57 95.2
8.5
95.2
95.2
95.1
83.8
72.5
61.2
49.9
86.7
9.1
86.7
86.7
86.6
75.3
64.0
52.7
41.4
4250
72 117.7
8.9
87.6
74.9
62.2
49.6
36.9
-
-
107.3
9.6
83.7
71.0
58.3
45.7
33.0
-
-
67 107.0
8.7
107.0
97.1
84.4
71.8
59.1
46.4
33.7
95.9
9.3
95.9
91.0
80.2
67.5
54.8
42.1
29.5
62 95.7
8.5
95.7
95.7
95.7
83.0
70.4
57.7
45.0
87.9
9.1
87.9
87.9
87.9
75.3
62.6
49.9
37.3
57 96.9
8.5
96.9
96.9
96.9
84.2
71.5
58.9
46.2
88.1
9.1
88.1
88.1
88.1
75.4
62.7
50.1
37.4
115°F
125°F
2550
72 88.0
10.0
54.3
47.1
39.8
32.5
25.3
-
-
79.1
10.7
50.7
43.4
36.1
28.8
21.6
-
-
67 77.2
9.7
70.0
62.8
55.5
48.2
40.9
33.7
26.4
67.7
10.2
65.8
58.5
51.2
44.0
36.7
29.4
22.1
62 72.9
9.6
72.9
71.8
64.5
57.3
50.0
42.7
35.5
66.3
10.2
66.3
64.7
57.4
50.1
42.9
35.6
28.3
57 72.1
9.6
72.1
71.9
64.6
57.3
50.1
42.8
35.5
64.6
10.2
64.6
64.3
57.0
49.7
42.4
35.2
27.9
2975
72 91.2
10.1
60.8
52.2
43.6
35.0
26.4
-
-
82.0
10.7
57.0
48.4
39.8
31.3
22.7
-
-
67 80.0
9.7
76.4
69.4
60.8
52.2
43.6
35.0
26.4
70.2
10.3
70.2
65.1
56.5
47.9
39.3
30.7
22.1
62 75.5
9.6
75.5
75.0
70.7
62.1
53.5
44.9
36.3
68.7
10.2
68.7
68.0
63.4
54.8
46.2
37.6
29.0
57 74.7
9.6
74.7
74.6
70.8
62.2
53.6
45.0
36.4
67.0
10.2
67.0
66.8
62.9
54.3
45.7
37.1
28.5
3400
72 94.5
10.1
67.2
57.3
47.4
37.5
27.6
-
-
84.9
10.8
63.4
53.5
43.6
33.7
23.7
-
-
67 82.8
9.8
82.8
76.0
66.1
56.2
46.3
36.4
26.4
72.6
10.4
72.6
71.7
61.8
51.9
41.9
32.0
22.1
62 78.2
9.7
78.2
78.2
76.9
67.0
57.1
47.1
37.2
71.2
10.3
71.2
71.2
69.3
59.4
49.5
39.6
29.6
57 77.4
9.7
77.4
77.4
77.0
67.1
57.1
47.2
37.3
69.3
10.3
69.3
69.3
68.8
58.9
49.0
39.1
29.2
3825
72 95.6
10.2
73.5
62.2
50.9
39.6
28.3
-
-
85.6
10.9
69.6
58.3
47.1
35.8
24.5
-
-
67 83.9
9.8
83.9
80.4
71.0
59.7
48.4
37.1
25.8
73.2
10.4
73.2
73.2
66.7
55.4
44.1
32.8
21.5
62 79.2
9.7
79.2
79.2
78.5
67.2
55.9
44.6
33.4
71.8
10.4
71.8
71.8
70.8
59.6
48.3
37.0
25.7
57 78.3
9.7
78.3
78.3
78.1
66.8
55.5
44.3
33.0
69.9
10.4
69.9
69.9
69.7
58.4
47.1
35.8
24.5
4250
72 96.8
10.2
79.8
67.1
54.4
41.8
29.1
-
-
86.3
10.9
75.9
63.2
50.5
37.9
25.2
-
-
67 84.9
9.9
84.9
84.9
75.9
63.2
50.5
37.9
25.2
73.8
10.5
73.8
73.8
71.6
58.9
46.3
33.6
20.9
62 80.2
9.8
80.2
80.2
80.2
67.5
54.8
42.1
29.5
72.4
10.4
72.4
72.4
72.4
59.7
47.0
34.4
21.7
57 79.3
9.8
79.3
79.3
79.3
66.6
53.9
41.3
28.6
70.5
10.4
70.5
70.5
70.5
57.8
45.1
32.5
19.8
*
The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.