DEFROSTING OPERATION (Available for heating only)
1.  Condition to start defrosting: Units will switch to defrosting 
mode when either of the following conditions is met.
a.  Unit  has  been  running  under T3  <  0ºC  for  40 
minutes and T3 < -3ºC for 3 minutes.
b.  Unit has been running at high temperature protection 
mode*  for  90  minutes.  (*High  temperature 
protection mode: when coil temperature of indoor 
unit reaches 55°C, outdoor unit will turn off external 
unit fan but still keep compressor running).
2.  Condition to stop defrosting: Units will switch back to 
heating mode when either of the following conditions 
is met.
a.  Unit has been running at defrosting mode for 10 
minutes.
b.  T3 > 20
 
ºC
Remark: T3 is coil temperature of outdoor units.
T3 (°C)
3 min
40 min
Heating mode
Defrosting mode
Time 
Elapsed 
(min)
Starting Defrosting Mode under condition a.
SERVICE AND MAINTENANCE
The units are designed to operate for long periods of time with a minimum of maintenance. However, the following 
operations must be performed regularly.
COMPONENT
MAINTENANCE OPERATIONS
RECOMMENDED FREQUENCY
Air filter
1 -  Clean  with  a  vacuum  cleaner  or  tap  gently 
then wash in warm water (40°C) with a mild 
detergent.
2 -  Rinse and dry before replacing on unit.
3 -  Never use petrol, alcohol or any other chemi-
cal product.
Every month or more often if
necessary.
Unit casing
1 -  Remove dust from the front panel with a soft 
duster or wipe a damp cloth with a mild soap 
solution.
2 -  Never use petrol, alcohol or any other chemi-
cal product.
Every month or more often if
necessary.
Drain pan and evacu-
ation piping
1 -  Clean and check for obstructions.
Each season before start up.
Indoor / Outdoor coils
1 -  Check  condition  and  remove  dust  from  be-
tween coil fins.
Each season before start up.
Compressor
1 -  No maintenance required.