11
 
TABLE 5: DNP036 COOLING CAPACITIES - 3 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,200 CFM
1,350 CFM
WB °F
WB °F
72
67
62
57
72
67
62
57
85 °F
NET CAP.
MBH
43.3
39.9
37.4
36.7
44
40.5
38
37.2
TOTAL POWER
INPUT kW
2.93
2.89
2.9
2.88
3.08
3.05
3.06
3.04
Sen
s
ib
le Cap
a
city
MBH
1
En
te
ring Dry
Bu
lb °F
86
29.5
35.8
37.4
36.7
31.8
38.4
38
37.2
83
26
32.3
37.4
36.7
27.8
34.4
38
37.2
80
22.5
28.8
34.8
35.6
23.8
30.4
36.7
36.7
77
19
25.3
31.3
32.1
19.9
26.4
32.7
32.7
74
15.5
21.8
27.8
28.6
15.9
22.5
28.7
28.7
71
-
18.3
24.3
25.1
-
18.5
24.7
24.7
68
-
14.8
20.8
21.6
-
14.5
20.7
20.7
95 °F
NET CAP.
MBH
41.4
37.1
35.7
35.3
42.5
38
36.6
36.2
TOTAL POWER
INPUT kW
3.22
3.27
3.18
3.15
3.32
3.37
3.28
3.25
S
e
n
s
ib
le
 C
apac
it
y
MB
H
1
Ent
e
ri
ng Dry
Bul
b
 °
F
86
28.5
34.8
35.7
35.3
31
36.9
36.6
36.2
83
25
31.3
35.7
35.3
27
33.7
36.6
36.2
80
21.5
27.8
33.5
33.9
23
29.7
25.5
35.5
77
18
24.3
30
30.4
19
25.7
31.5
31.5
74
14.5
20.8
26.5
26.9
15
21.7
17.6
27.5
71
-
17.3
23
23.4
-
17.7
23.6
23.5
68
-
13.8
19.5
19.9
-
13.8
19.6
19.5
105 °F
NET CAP.
MBH
38.5
34.8
33.9
33.6
39.6
35.8
34.8
34.5
TOTAL POWER
INPUT kW
3.61
3.61
3.5
3.48
3.73
3.72
3.61
3.59
S
ensible
 Cap
a
city
MBH
1
Ent
e
rin
g
 Dr
y
Bulb
 °
F
86
27.6
33.6
33.9
33.6
29.9
35.1
34.8
34. 5
83
24.1
30.1
33.9
33.6
26
32.4
34.8
34.5
80
20.6
26.6
32
32.2
22
28.4
33.9
33.8
77
17.1
23.1
28.5
28.7
18
24.4
29.9
29.8
74
13.6
19.6
25
25.2
14
20.5
25.9
25.8
71
-
16.1
21.5
21.7
-
16.5
21.9
21.8
68
-
12.6
18
18.2
-
12.5
18
17.9
115 °F
NET CAP.
MBH
35.6
32.6
32.2
31.9
36.7
33.5
33.1
32.8
TOTAL POWER
INPUT kW
4.01
3.95
3.82
3.8
4.14
4.07
3.93
3.92
Se
nsible Cap
a
city
MBH
1
En
te
ri
n
g
 D
ry
Bu
lb
 °
F
86
26.6
32.4
32.2
31.9
28.9
33.4
33.1
32.8
83
23.1
28.9
32.2
31.9
24.9
31.1
33.1
32.8
80
19.6
25.4
30.6
30.6
21
27.1
32.3
32.1
77
16.1
21.9
27.1
27.1
17
23.2
28.3
28.1
74
12.6
18.4
23.6
23.6
13
19.2
24.3
24.1
71
-
14.9
20.1
20.1
-
15.2
20.3
20.2
68
-
11.4
16.6
16.6
-
11.2
16.3
16.2
125 °F
NET CAP.
MBH
32.8
30.2
30.4
30.1
33.7
31.2
31.3
30
TOTAL POWER
INPUT kW
4.4
4.3
4.1
4.1
4.5
4.4
4.3
4.2
Sen
s
ib
le Cap
a
city
MB
H
1
En
te
ring Dry
Bu
lb °F
86
25.6
31.2
30.4
30.1
27.9
31.6
31.3
31
83
22.1
27.7
30.4
30.1
23.9
29.9
31.3
31
80
18.6
24.2
19.1
28.9
19.9
25.9
30.6
30.4
77
15.1
20.7
25.6
25.4
15.9
21.9
26.6
26.4
74
11.6
17.2
22.1
21.9
12
17.9
22.7
22.5
71
-
13.7
18.6
18.4
-
13.9
18.7
18.5
68
-
10.2
15.1
14.9
-
9.9
14.7
14.5
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY