York DNP036 User Manual

Page of 36
036-21366-007-A-1205
Unitary Products Group
9
  
TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
125°F
NET 
CAP.
MBH
POWER
INPUT
KW
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
600
72
18.4 
2.5 
13.1 
11.4 9.7 8.0 6.3 #N/A
#N/A
67
16.6 2.4 16.7 15.0 13.3 11.5  9.8  8.1 
6.4 
62
16.2 2.5 16.2 
16.2 14.8 13.1 11.4  9.6 
7.9 
57
16.5 2.5 16.5 
16.5 14.9 13.2 11.5  9.8 
8.1 
700
72
19.3 2.6 14.6 
12.5 
10.5 
8.5 
6.5 
#N/A
#N/A
67
17.4 2.5 17.8 16.4 14.4 12.4 10.3  8.3 
6.3 
62
17.0 2.5 17.0 
17.0 16.0 14.0 12.0  10.0  7.9 
57
17.2 2.5 17.2 
17.2 16.2 14.2 12.1  10.1  8.1 
800
72
20.1 2.6 16.0 
13.7 
11.3 
9.0 
6.7 
#N/A
#N/A
67
18.1 2.5 18.9 17.9 15.5 13.2 10.9  8.5 
6.2 
62
17.7 2.5 17.7 
17.7 17.3 15.0 12.6  10.3  8.0 
57
18.0 2.5 18.0 
18.0 17.5 15.1 12.8  10.5  8.1 
900
72
20.4 2.6 17.1 
14.5 
11.8 
9.2 
6.5 
#N/A
#N/A
67
18.3 2.6 18.7 
18.6 16.2 13.5 10.9  8.2 
5.6 
62
17.9 2.6 17.9 
17.9 17.7 15.0 12.4  9.7 
7.1 
57
18.2 2.6 18.2 
18.2 17.9 15.3 12.6  9.9 
7.3 
1000
72
20.6 2.7 18.3 
15.3 
12.3 
9.3 
6.3 
#N/A
#N/A
67
18.5 2.6 18.5 
19.3 16.9 13.9 10.9  7.9 
4.9 
62
18.1 2.6 18.1 
18.1 
18.1 15.1 12.1  9.2 
6.2 
57
18.4 2.7 18.4 
18.4 
18.4 15.4 12.4  9.4 
6.5 
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY