Unitary Products Group
TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER
MODEL
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE
MOTOR PULLEY
FIXED
BLOWER PULLEY
BELT
HP
RPM
FRAME
SIZE
SERVICE
FACTOR
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
LENGHT
(in.)
DESIG-
NATION
DHE/DHG 036
780 - 1120
1
1/
2
1,725
56
1.15
2.4 - 3.4
7/
8
5.7
1
37.3
A36
DHE/DHG048
790 - 1,120
1
1/
2
1,725
56
1.15
2.4 - 3.4
7/
8
5.7
1
37.3
A36
DHE/DHG060
850 - 1,220
1
1/
2
1,725
56
1.15
2.4 - 3.4
7/
8
5.2
1
37.3
A36
1.
All motors have solid bases and are inherently protected.  These motors can be selected to operate into their service factor 
because they are located in the moving air, upstream of any heating device
TABLE 14: ELECTRICAL DATA - BASIC UNIT
MODEL
DHE/
DHG
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR
FLA
SUPPLY
AIR
AMPACITY
AMPS
TOTAL
UNIT
AMPACITY
AMPS
MAX.
FUSE
SIZE
2
AMPS
MAX.
HACR
BREAKER
SIZE
AMPS
MIN.
MAX.
RLA
LRA
036
208/230-3-60
187
253
14.1
110
2.3
5.3
25.2
35
35
460-3-60
414
504
7.1
54
1.4
3.1
13.3
20
20
048
208/230-3-60
187
253
10.0
110.0
2.3
5.2
23.9
35
35
460-3-60
414
504
5.2
54.0
1.4
2.6
12.4
15
15
060
208/230-3-60
187
253
16.0
137.0
2.3
6.0
28.3
40
40
460-3-60
414
504
8.3
69.0
1.4
3.0
14.8
20
20
1.
Rated in accordance with ARI Standard 110, utilization range “A”..