York D2HE/D2HG060 User Manual

Page of 28
036-21216-003-A-0204
16
Unitary Products Group
TABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060
MODEL
DHE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
TOTAL
UNIT
AMPACITY
AMPS
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
AMPS
kW
STAGES
TOTAL
AMPS
060
208-3-60
2CE04500525
3
6.0
4.0
1
11.0
26.0
40
40
2CE04500725
4
5.6
1
15.6
26.9
40
40
2CE04501025
8.0
1
22.1
35.1
40
40
2CE04501525
11.9
2
33.1
48.9
50
50
2CE04502025
15.9
2
44.2
62.7
70
70
2CE04503025
22.2
2
61.7
84.6
90
90
230-3-60
2CE04500525
4
6.0
5.3
1
12.7
26.0
40
40
2CE04500725
4
7.5
1
18.0
30.1
40
40
2CE04501025
10.6
1
25.5
39.4
40
40
2CE04501525
15.9
2
38.2
55.3
60
60
2CE04502025
21.2
2
51.0
71.2
80
80
2CE04503025
29.6
2
71.2
96.5
100
100
460-3-60
2CE04500746
4
3.0
6.8
1
8.2
14.0
20
20
2CE04501046
4
10.1
1
12.1
18.9
20
20
2CE04501546
4
13.6
1
16.4
24.2
25
25
2CE04502046
4
19.5
2
23.5
33.1
35
35
2CE04503046
4
28.8
2
34.6
47.1
50
50
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box.  If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17 
for fuse block accessories available for field installation.
FIGURE 2 -  FIELD POWER WIRING
FIGURE 3 -  CONTROL WIRING COOLING ONLY
R V
Y C
G F
R
Y 1
B
Y 2
T H E R M O S T A T
1
T E R M I N A L S
U N I T   T E R M I N A L
S T R I P   T B 1
2 4   V O L T
T R A N S F O R M E R
C O O L I N G   O N L Y   ( 2 4   V O L T   T H E R M O S T A T )
1 2 4   V O L T   T H E R M O S T A T   2 T H 0 7 7 0 1 0 2 4   I F   T H E   U N I T   H A S   A N   E C O N O M I Z E R ,
R E M O V E   J U M P E R   J 1   F R O M   T E R M I N A L S   8   A N D   1 0   O N   T H E   R E L A Y   B O A R D  
T O   P R E V E N T   S I M U L T A N E O U S   O P E R A T I O N   O F   T H E   C O M P R E S S O R   A N D
T H E   E C O N O M I Z E R .     I F   Y O U   W A N T   T O   C O N T R O L   T H E   E C O N O M I Z E R   O N   A
S E C O N D   S T A G E   O F   C O O L I N G ,   U S E   T H E   T H E R M O S T A T   2 T H 0 4 7 0 1 2 2 4 .