York D3CG User Manual

Page of 20
UNIT
SIZE
POWER
SUPPLY
COMPRESSOR
OUTDOOR
FAN
MOTOR,
(#1 & #2)
FLA, EACH
SUPPLY AIR
BLOWER
MOTOR, (FLA)
TOTAL UNIT
AMPACITY,
(AMPS)
MAX.
FUSE
SIZE
1
MIN.
WIRE SIZE
2
,
(mm
2
/AWG)
RLA
LRA
3 kW 
4 HP
5.6 kW
7.5 HP 
3 kW
4 HP
5.6 kW
7.5 HP
#1
#2
#1
#2
180
380/400/415-3+N-50
19.2
9.6
146
73
2.4
8.6
-
47.0
-
60
10 / 8
240
380/400/415-3+N-50
19.2
19.2
146
146
2.4
-
11.7
-
59.7
70
16 / 6
NOTES:
1. Slow blow type fuse.
2. Based on 105
°
C insulated copper conductors in conduit.
24 VOLT
TRANSFORMER
ELECTRICAL DATA 
-
 Cooling Only Units and Units With Gas Heat
FIELD WIRING - Electric/Electric and Gas/Electric Units
GRD.  LUG
LINE VOLTAGE
TERMINAL
BLOCK 2TB
IN UNIT
CONTROL BOX
L1
L2
L3
N
NEUTRAL
TERMINAL
Refer to the 
ELECTRICAL DATA
tables to size the
power wiring, the fuses and
the disconnect switch.