UNIT
SIZE
POWER
SUPPLY
(VOLTS)
HEATER  OPTION
MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
FUSE SIZE
1
MINIMUM
WIRE SIZE
2
(mm
2
/AWG)
MODEL
OUTPUT
kW
STAGES
AMPS
180
380-3+N-50
E018
E036
E054
E072
11.3
22.6
33.8
45.1
1
2
2
2
17.1
34.3
51.4
68.6
 47.0
 53.6
 75.0
 96.5
 60
 60
 80
100
10 / 8
16 / 6
25 / 4
35 / 2
415-3+N-50
E018
E036
E054
E072
13.5
26.9
40.4
53.8
1
2
2
2
18.7
37.4
56.2
 74.9 
 47.0
 57.5
 80.9
104.0
 60
 60
 90
110
10 / 8
16 / 6
25 / 4
35 / 2
240
380-3+N-50
E018
E036
E054
E072
11.3
22.6
33.8
45.1
1
2
2
2
17.1
34.3
51.4
68.6
 59.7
 59.7
 78.9
100.0
 70
 70
 80
110
16 / 6
16 / 6
25 / 4
35 / 2
415-3+N-50
E018
E036
E054
E072
13.5
26.9
40.4
53.8
1
2
2
2
18.7
37.4
56.2
74.9
 59.7
 61.4
 84.8
108.0
 70
 70
 90
110
16 / 6
16 / 6
25 / 4
50 / 2
NOTES:
1. Slow blow type fuse.
2. Based on 105
°
C copper conductors.
WEIGHTS (kg. / lbs.)
BASIC
UNIT
D*CE UNITS
180
866 / 1910
240
957 / 2110
D*CG UNITS
180
975 / 2150 
240
1066 / 2350
OPTIONS / ACCESSORIES
Economizer
73 / 160
Motorized Damper
68 / 150
Electric
Heaters
18 kW
11 / 25
36 kW
14 / 30
54 kW
16 / 35
72 kW
18 / 40
Roof Curb
180
79 / 175
240
84 / 185
Barometric Damper
20 / 45
Wood
Skid*
180
91 / 200 
240
100 / 220
*
Allows handling of unit using 2300mm (90")
  long forks.
COMPONENT DESCRIPTION
UNIT SIZE (MBH)
180
240
SUPPLY AIR
BLOWER
CENTRIFUGAL BLOWER
DIA. x WD. (mm)
381 x 381
457 x 381
DIA. x WD. (in.)
15 x 15
18 x 15
FAN MOTOR
kW / HP
3.7 / 5
5.6 / 7.5
INDOOR
COIL
ROWS DEEP
3
3
FINS PER 25mm (1 in.)
13.5
13.5
FACE AREA
m
2
  / Ft.
2
1.45 / 15.5
1.92 / 20.5
OUTDOOR
FANS
(Two Per Unit)
PROPELLER DIA.
mm / in.
762 / 30  (ea.) 762 / 30 (ea.)
FAN MOTOR
kW / HP
0.7 / 1 (ea.)
0.7 / 1 (ea.)
NOMINAL AIRFLOW
m
3
 / s
2.83 (ea.)
3.78 (ea.)
CFM
6000 (ea.)
8000 (ea.)
OUTDOOR
COIL
ROWS DEEP
2
2
FINS PER 25mm (1 in.)
13
20
FACE AREA 
m
2
  / Ft.
2
3.35 / 36.0
4.02 / 43.3
COMPRESSOR
(Qty. Per Unit)
TANDEM (10 TON NOMINAL CAPACITY)
1*
2
HERMETIC (5 TON NOMINAL CAPACITY)
1
-
AIR
FILTERS
QUANTITY PER UNIT
406 x 508 x 51 (mm)
-
4
16 x 20 x 2 (in.)
QUANTITY PER UNIT
406 x 635 x 51 (mm)
-
4
16 x 25 x 2 (in.)
QUANTITY PER UNIT
457 x 610 x 51 (mm)
5
-
18 x 24 x 2 (in.)
TOTAL FACE AREA
m
2
  / Ft.
2
1.40 / 15.0
1.87 / 20.0
CHARGE
REFRIGERANT 22
SYS. #1 ( kg. / lbs.)
7.94 / 17.5
8.16 / 18.0
SYS. #2 (kg. / lbs.)
3.86 / 8.5
8.16 / 18.0
*
This compressor will be energized first.