York D2NA060 User Manual

Page of 21
Refer to Figure 5 for information concerning rear and bottom
supply and return air duct openings.
ROOF CURB
On applications when a roof curb is used, the unit must be posi-
tioned on the curb so the front of the unit is tight against the
curb.
FILTERS
Single phase units are shipped without a filter and is the responsi-
bility of the installer to secure a filter in the return air ductwork or
install a Filter/Frame Kit 
(1FF0110 for the D1NA018 thru
D1NA042 and 1FF0112 for the D1NA048 and D2NA060).
A filter rack and filters are standard on three phase units.
NOTE: Filters on the D1NA048 and D2NA060 units require
the use of a
5
16
" nut driver for removal.
Filters must always be used and must be kept clean. When fil-
ters become dirt laden, insufficient air will be delivered by the
blower, decreasing your units efficiency and increasing operat-
ing costs and wear-and-tear on the unit and controls.
Filters should be checked monthly especially since this unit is
used for both heating and cooling.
CONDENSATE DRAIN
A condensate trap is recommended to be installed in the con-
densate drain. The plumbing must conform to local codes. Use
a sealing compound on male pipe threads. Install the conden-
sate drain line (
3
4
“ NPTF) to spill into an open drain.
SERVICE ACCESS
Access to all serviceable components is provided by the follow-
ing removable panels:
Blower compartment
Gas control/electrical service access
Refer to Figure 5 for location of these access panels and mini-
mum clearances.
THERMOSTAT
The room thermostat should be located on an inside wall ap-
proximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appli-
ances. Follow manufacturer's instructions enclosed with the
thermostat for general installation procedure. Four color coded
insulated wires (minimum #18 AWG) should be used to con-
nect thermostat to unit. See Figure 1.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage tol-
erances which must be maintained at the compressor termi-
nals during starting and running conditions are indicated on the
unit Rating Plate and Table 8.
The wiring entering the cabinet must be provided with me-
chanical strain relief.
A fused disconnect switch should be field provided for the unit. If
any of the wire supplied with the unit must be replaced, replace-
ment wire must be of the type shown on the wiring diagram.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.
Refer to Figure 1 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.
COMPRESSORS
Units are shipped with compressor mountings factory-adjusted
for shipping. CAUTION: Loosen compressor mounting bolts
half turn before operating unit.
035-18265-001-A-0202
4
Unitary Products Group
FIG. 1 - TYPICAL FIELD WIRING DIAGRAM
P O W E R
WIRING
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
CAUTION: Label all wires prior
to disconnection when
servicing controls.
Wiring errors can cause
improper and dangerous
operation. Verify proper
operation after servicing.
R
G
W
R
G
C
Y
Y
W
C
CONTROL WIRING
THERMOSTAT
24 VOLT
TRANSFORMER
PROGRAMABLE
THERMOSTAT ONLY
** = Minimum wire size of 18 AWG
wire shuold be used for all field
installed 24 volt wire.
REFER TO ELECTRICAL
DATA TABLES TO SIZE THE
DISCONNECT SWITCH,
WIRING & OVERCURRENT
REFER TO ELECTRICAL
DATA TABLES TO SIZE THE
DISCONNECT SWITCH,
WIRING & OVERCURRENT