York D2NA060 User Manual

Page of 21
3. Use wrought iron or steel pipe for all gas lines. Pipe dope
should be applied sparingly to male threads only.
CAUTION: If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel
pipe must be installed at the gas valve and extend a
minimum of two (2) inches outside of the unit casing.
WARNING: Natural gas may contain some propane. Propane,
being an excellent solvent, will quickly dissolve
white lead or most standard commercial com-
pounds. Therefore, a special pipe dope must be
applied when wrought iron or steel pipe is used.
Shellac base compounds such as Gaskolac or Sta-
lastic, and compounds such as Rectorseal #5,
Clyde's or John Crane may be used.
4. All piping should be cleaned of dirt and scale by hammering
on the outside of the pipe and blowing out the loose dirt and
scale. Before initial start-up, be sure that all of the gas lines
external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in ac-
cordance with all safety codes as prescribed under “Limita-
tions”. After the gas connections have been completed, open
the main shut-off valve admitting normal gas pressure to the
mains. Check all joints for leaks with soap solution or other
material suitable for the purpose. NEVER USE A FLAME.
6. The furnace and its individual manual shut-off valve must
be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in ex-
cess of 1/2 psig (3.48 kPa).
The furnace must be isoulated from the gas supply piping
system by closing its individual manual shut-off valve dur-
ing any pressure testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig (3.48 kPa).
FLUE VENT HOOD
The flue vent hood with screen is not shipped attached. This hood
must be installed to assure proper unit operation. The hood must
be fastened to the outside of the side gas control/electrical com-
partment with the screws provided in the bag attached to the in-
side of the gas control/electrical compartment, see Figure 3.
The unit is controlled by a conventional four wire heating/cool-
ing thermostat common to this class of equipment.
035-18265-001-A-0202
6
Unitary Products Group
V E N T   O U T L E T   S C R E E N
F L U E   V E N T   O U T L E T
A I R   H O O D
FIG. 3 - FLUE VENT OUTLET AIR HOOD
TABLE 6 - PHYSICAL DATA
MODELS
DNA
018
024
030
036
042
048
060
EVAPORATOR
BLOWER
CENTRIFUGAL BLOWER (Dia. x Wd. in.)
10 X 8
10 X 8
10 X 8
11 x 10
11 x 10
12 x 11
12 x 11
FAN MOTOR HP (Three Speed)
1
2
1
2
1
2
3
4
3
4
1.0
1.0
EVAPORATOR
COIL
ROWS DEEP
2
2
2
2
3
3
3
FINS PER INCH
14
13
13
15
13
13
13
FACE AREA (Sq. Ft.)
2.25
3.5
3.5
3.5
3.5
4.5
4.5
CONDENSER
FAN
PROPELLER DIA. (in.)
22
22
22
22
22
22
22
FAN MOTOR HP
1
4
1
4
1
4
1
4
1
4
1
4
1
4
NOM. CFM TOTAL
1,800
2,200
2,400
2,400
2,400
3,000
3,000
CONDENSER
COIL
ROWS DEEP
1
1
1
1
1
1
1
FINS PER INCH
13
13
16
20
20
20
20
FACE AREA (Sq. Ft.)
8.3
8.3
11.7
11.7
11.7
14.8
14.8
CHARGE
REFRIGERANT 22 (lbs./oz.)
3 / 2
3 / 6
4 / 12
4 / 3
4 / 12
6 / 0
5 / 4
FILTER*
FACE AREA (Sq. Ft.) / SIZE (NOMINAL)
2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 2.6/20x20 3.3/20x12 3.3/20x12
FURNACE
SECTION
NATURAL GAS BURNER ORIFICE NO.
(Qty./Drill size)
43
43
43
43
43
40
40
PROPANE BURNER ORIFICE NO.
(Qty./Drill size)
55
55
55
55
55
53
53
GAS CONNECTION SIZE
1
2
NPTI
1
2
NPTI
1
2
NPTI
1
2
NPTI
1
2
NPTI
1
2
NPTI
1
2
NPTI
COMPRESSOR
TYPE
HERMETICALLY SEALED
(R = RECIPROCATING,   S = Scroll)
R
R
R
R
R
S
S
* = Three phase 018 thru 042 size units are supplied with one (1) filter and on three phase 048 and 060 size units two (2) filters are supplied. Single phase units are shipped without filters.
See “FILTERS” on page 4.
WARNING: FLUE HOOD SURFACES
MAY BE HOT.
CAUTION
The flue exhaust hood must be properly installed and within the
recommended clearances. Further communications and action
must be given to the home or building owner(s) to eleiminate
any unauthorized humon contact around this area during the
heating cycle. Flue hood surface and immediate area is de-
signed to operate at high temperatures during the heating cycle.