York DM120 User Manual

Page of 36
036-21044-003-A-0304
14
Unitary Products
TABLE 4: COOLING CAPACITY 7-1/2 TON UNIT - IMPERIAL
Air On
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Temperature of Air on Condenser Coil 95°F
CFM
WB
(°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2250
72 
104
8.6
60
54
47
41
34
-
-
98
9.2
57
50
44
37
31
-
-
67 
96
8.4
74
68
61
55
48
42
35
90
9.0
71
64
58
51
45
39
32
62 
88
8.2
87
81
75
68
62
55
49
80
8.6
80
75
69
63
56
50
43
57 
84
8.2
84
83
77
71
64
58
51
78
8.6
78
77
71
64
58
51
45
2625
72 
107
8.7
66
59
51
43
36
-
-
101
9.3
63
55
48
40
32
-
-
67 
99
8.5
81
73
66
58
51
43
35
92
9.1
78
71
63
55
48
40
33
62 
90
8.3
90
87
80
73
65
58
50
83
8.7
83
80
75
68
60
52
45
57 
87
8.2
87
86
83
75
68
60
53
81
8.7
81
80
77
69
62
54
46
3000
72 
110
8.8
72
63
55
46
37
-
-
104
9.4
69
60
51
43
34
-
-
67 
102
8.6
88
79
71
62
53
44
36
95
9.2
86
77
68
59
51
42
33
62 
93
8.3
93
93
86
77
69
60
51
86
8.8
86
86
81
72
64
55
46
57 
89
8.3
89
89
89
80
71
63
54
83
8.8
83
83
83
74
66
57
48
3375
72 
112
8.8
77
68
58
48
38
-
-
106
9.4
74
64
54
44
34
-
-
67 
104
8.6
94
84
74
64
54
44
35
97
9.2
92
82
72
62
52
42
32
62 
95
8.4
95
95
91
81
71
61
51
87
8.9
87
87
85
75
65
55
45
57 
91
8.3
91
91
91
81
71
61
51
84
8.9
84
84
84
74
64
55
45
3750
72 
115
8.9
83
72
61
49
38
-
-
108
9.5
79
68
57
46
34
-
-
67 
106
8.7
101
89
78
67
56
45
33
99
9.3
97
86
75
64
53
42
30
62 
97
8.4
97
97
95
84
73
62
51
88
8.9
88
88
88
77
66
55
44
57 
92
8.4
92
92
92
81
70
59
48
86
8.9
86
86
86
75
63
52
41
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
2250
72 
91
9.8
54
48
41
35
28
-
-
84
10.4
51
45
39
32
26
-
-
67 
81
9.5
67
61
54
48
42
35
29
73
10.0
64
57
51
45
38
32
25
62 
73
9.1
73
71
64
58
51
45
38
66
9.7
66
66
59
53
46
40
34
57 
71
9.1
71
71
64
58
52
45
39
65
9.7
65
65
58
52
45
39
33
2625
72 
94
9.9
60
52
45
37
30
-
-
87
10.5
57
50
42
35
27
-
-
67 
84
9.6
74
67
59
52
44
37
29
76
10.1
71
63
56
48
40
33
25
62 
75
9.3
75
74
70
62
55
47
40
68
9.8
68
68
65
57
49
42
34
57 
74
9.3
74
73
70
63
55
47
40
67
9.8
67
67
64
56
48
41
33
3000
72 
97
10.0
66
57
49
40
31
-
-
89
10.6
63
54
46
37
28
-
-
67 
87
9.7
82
73
64
55
47
38
29
78
10.2
78
69
60
52
43
34
25
62 
78
9.4
78
78
76
67
58
49
41
70
9.9
70
70
70
61
53
44
35
57 
76
9.4
76
76
76
67
58
50
41
69
9.9
69
69
69
60
51
43
34
3375
72 
99
10.1
71
61
51
41
31
-
-
91
10.7
68
58
48
38
28
-
-
67 
88
9.8
85
78
68
58
48
38
28
80
10.3
79
74
64
54
44
34
24
62 
79
9.4
79
79
78
68
58
48
38
71
10.0
71
71
71
61
51
42
32
57 
77
9.4
77
77
77
67
57
47
37
70
10.0
70
70
70
60
50
40
30
3750
72 
101
10.1
76
65
54
43
32
-
-
93
10.8
73
62
51
40
29
-
-
67 
90
9.8
89
82
71
60
49
38
27
81
10.4
81
79
67
56
45
34
23
62 
81
9.5
81
81
81
69
58
47
36
73
10.1
73
73
73
62
50
39
28
57 
79
9.5
79
79
79
68
56
45
34
72
10.1
72
72
72
60
49
38
27
Temperature of Air on Condenser Coil 125°F
2250
72 
77
11.0
49
42
36
30
23
-
-
67 
65
10.5
60
54
48
41
35
28
22
62 
59
10.2
59
59
54
48
42
35
29
57 
58
10.2
58
58
52
46
39
33
26
2625
72 
80
11.1
55
47
39
32
24
-
-
67 
67
10.6
67
60
52
44
37
29
22
62 
60
10.3
60
60
59
52
44
37
29
57 
60
10.3
60
60
57
49
42
34
27
3000
72 
82
11.2
60
51
43
34
25
-
-
67 
69
10.8
69
65
56
48
39
30
21
62 
62
10.4
62
62
62
56
47
38
29
57 
62
10.5
62
62
62
53
44
36
27
3375
72 
84
11.4
65
55
45
35
26
-
-
67 
71
10.9
71
70
60
50
40
30
20
62 
64
10.5
64
64
64
55
45
35
25
57 
63
10.6
63
63
63
53
43
33
23
3750
72 
85
11.5
70
59
48
37
26
-
-
67 
72
11.0
72
72
63
52
41
30
19
62 
65
10.6
65
65
65
54
43
31
20
57 
64
10.7
64
64
64
53
42
31
20
1 These capacities are gross ratings.  For net 
capacity, deduct air blower motor, MBH = 3.415 
x kW.  Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air 
blower motor.
2 These ratings include condenser fan motors  
and the compressor motors but not the supply 
air blower motor.