Page of 36
036-21044-003-A-0304
Unitary Products
15
TABLE 5: COOLING CAPACITY 26.4 KW UNIT - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 29°C
Temperature of Air on Condenser Coil 35°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°F)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
1.06
22
31
8.6
18
16
14
12
10
-
-
29
9.2
17
15
13
11
9
-
-
19
28
8.4
22
20
18
16
14
12
10
26
9.0
21
19
17
15
13
11
9
17
26
8.2
26
24
22
20
18
16
14
24
8.6
24
22
20
18
16
15
13
14
25
8.2
25
24
23
21
19
17
15
23
8.6
23
23
21
19
17
15
13
1.24
22
31
8.7
19
17
15
13
10
-
-
30
9.3
18
16
14
12
9
-
-
19
29
8.5
24
22
19
17
15
13
10
27
9.1
23
21
18
16
14
12
10
17
27
8.3
26
26
24
21
19
17
15
24
8.7
24
24
22
20
18
15
13
14
25
8.2
25
25
24
22
20
18
15
24
8.7
24
23
23
20
18
16
14
1.42
22
32
8.8
21
19
16
13
11
-
-
31
9.4
20
18
15
13
10
-
-
19
30
8.6
26
23
21
18
16
13
10
28
9.2
25
23
20
17
15
12
10
17
27
8.3
27
27
25
23
20
18
15
25
8.8
25
25
24
21
19
16
14
14
26
8.3
26
26
26
24
21
18
16
24
8.8
24
24
24
22
19
17
14
1.59
22
33
8.8
23
20
17
14
11
-
-
31
9.4
22
19
16
13
10
-
-
19
30
8.6
28
25
22
19
16
13
10
28
9.2
27
24
21
18
15
12
9
17
28
8.4
28
28
27
24
21
18
15
25
8.9
25
25
25
22
19
16
13
14
27
8.3
27
27
27
24
21
18
15
25
8.9
25
25
25
22
19
16
13
1.77
22
34
8.9
24
21
18
14
11
-
-
32
9.5
23
20
17
13
10
-
-
19
31
8.7
29
26
23
20
16
13
10
29
9.3
29
25
22
19
15
12
9
17
28
8.4
28
28
28
25
21
18
15
26
8.9
26
26
26
23
19
16
13
14
27
8.4
27
27
27
24
21
17
14
25
8.9
25
25
25
22
19
15
12
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
1.06
22
27
9.8
16
14
12
10
8
-
-
25
10.4
15
13
11
9
8
-
-
19
24
9.5
20
18
16
14
12
10
8
21
10.0
19
17
15
13
11
9
7
17
21
9.1
21
21
19
17
15
13
11
19
9.7
19
19
17
15
14
12
10
14
21
9.1
21
21
19
17
15
13
11
19
9.7
19
19
17
15
13
11
10
1.24
22
28
9.9
18
15
13
11
9
-
-
25
10.5
17
15
12
10
8
-
-
19
25
9.6
22
20
17
15
13
11
8
22
10.1
21
19
16
14
12
10
7
17
22
9.3
22
22
20
18
16
14
12
20
9.8
20
20
19
17
14
12
10
14
22
9.3
22
22
21
18
16
14
12
20
9.8
20
20
19
16
14
12
10
1.42
22
28
10.0
19
17
14
12
9
-
-
26
10.6
19
16
13
11
8
-
-
19
25
9.7
24
21
19
16
14
11
9
23
10.2
23
20
18
15
13
10
7
17
23
9.4
23
23
22
20
17
14
12
21
9.9
21
21
21
18
15
13
10
14
22
9.4
22
22
22
20
17
15
12
20
9.9
20
20
20
18
15
12
10
1.59
22
29
10.1
21
18
15
12
9
-
-
27
10.7
20
17
14
11
8
-
-
19
26
9.8
25
23
20
17
14
11
8
23
10.3
23
22
19
16
13
10
7
17
23
9.4
23
23
23
20
17
14
11
21
10.0
21
21
21
18
15
12
9
14
23
9.4
23
23
23
20
17
14
11
21
10.0
21
21
21
18
15
12
9
1.77
22
29
10.1
22
19
16
13
9
-
-
27
10.8
21
18
15
12
8
-
-
19
26
9.8
26
24
21
18
14
11
8
24
10.4
24
23
20
16
13
10
7
17
24
9.5
24
24
24
20
17
14
11
21
10.1
21
21
21
18
15
12
8
14
23
9.5
23
23
23
20
17
13
10
21
10.1
21
21
21
18
14
11
8
Temperature of Air on Condenser Coil 52°C
1.06
22
23
11.0
14
12
11
9
7
-
-
19
19
10.5
18
16
14
12
10
8
6
17
17
10.2
17
17
16
14
12
10
8
14
17
10.2
17
17
15
13
12
10
8
1.24
22
23
11.1
16
14
12
9
7
-
-
19
20
10.6
20
17
15
13
11
9
6
17
18
10.3
18
18
17
15
13
11
9
14
18
10.3
18
18
17
14
12
10
8
1.42
22
24
11.2
18
15
13
10
7
-
-
19
20
10.8
20
19
17
14
11
9
6
17
18
10.4
18
18
18
16
14
11
9
14
18
10.5
18
18
18
16
13
10
8
1.59
22
25
11.4
19
16
13
10
7
-
-
19
21
10.9
21
20
18
15
12
9
6
17
19
10.5
19
19
19
16
13
10
7
14
19
10.6
19
19
19
16
13
10
7
1.77
22
25
11.5
21
17
14
11
8
-
-
19
21
11.0
21
21
19
15
12
9
5
17
19
10.6
19
19
19
16
12
9
6
14
19
10.7
19
19
19
16
12
9
6
1 These capacities are gross ratings.  For net 
capacity, deduct air blower motor.  Refer to the 
appropriate Blower Performance Table for the 
kW of the supply air blower motor.
2 These ratings include condenser fan motors  
and the compressor motors but not the supply 
air blower motor.