FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers, 
phase monitor, dirty filter switch, and coil guard to make them 
suitable for almost every application.
All units are self-contained and assembled on full perimeter 
base rails with holes in the four corners for overhead rigging. 
Every unit is completely piped, wired, charged and tested at 
the factory to simplify the field installation and to provide 
years of dependable operation.
All models (including those with an economizer) are suitable 
for either bottom or horizontal duct connections. Models with 
factory installed power exhaust are suitable for bottom 
duct connections only
. For bottom duct, you remove the 
sheet metal panels from the supply and return air openings 
through the base of the unit. For horizontal duct, you replace 
the supply and return air panels on the rear of the unit with a 
side duct flange accessory.
All models are available with these “factory mounted” outdoor 
air damper options:
Single enthalpy economizer with or without power 
exhaust
BAS-ready economizer with or without power exhaust
Motorized outdoor air damper
Barometric Relief Damper
A fixed outdoor air intake assembly will be shipped in the 
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly 
includes a rain hood with a damper that can be set for 10, 15 
or 25% outdoor air. With bottom duct connections, the intake 
damper assembly should be mounted over the opening in the 
return air panel. With horizontal ductwork, it should be 
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can 
be adjusted to meet the exact requirements of the job. A high 
static drive option is available for applications with a higher 
CFM and/or static pressure requirement. A variable air vol-
ume (VAV) option using a variable frequency drive is available 
for applications requiring a constant supply duct pressure. A 
differential pressure transducer is used to monitor supply duct 
static pressure and return a speed reference signal to the VFD 
to control the output of the indoor blower motor.
All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion 
valve, a liquid line filter-drier, a discharge line high pressure 
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot 
gas bypass option, consisting of an adjustable compressor 
discharge bypass valve, is available for low cooling load 
applications.
Simplicity®  Controls - Simplicity® control boards have 
standardized a number of features previously available 
only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control 
allows all units to operate in the cooling mode down 
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the 
outdoor air temperature is low or when free cooling 
is available.
Anti-Short Cycle Protection - To aid compressor 
life, an anti-short cycle delay is incorporated into the 
standard controls. Compressor reliability is further 
ensured by programmable minimum run times. For 
testing, the anti short cycle delay can be temporarily 
overridden with the push of a button.
Lead-Lag - An integrated Lead-Lag option allows 
equal run time hours on all compressors, thereby 
extending the life of all compressors. This option is 
selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling 
fan delay times are independent of one another. All 
units are programmed with default values based 
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the 
high and low-pressure switches, the freezestats, the 
gas valve, if applicable, and the temperature limit 
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor 
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent 
nuisance trouble calls, the control board uses a 
“three times, you’re out” philosophy. The high and 
low-pressure switches and the freezestats must trip 
three times within two hours before the unit control 
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a 
trouble light on the thermostat, if so equipped, and 
flash an alarm code on the control board LED. Each 
high and low-pressure switch alarm as well as each 
freezestat alarm has its own flash code. The control 
board saves the five most recent alarms in memory, 
and these alarms can be reviewed at any time. 
Alarms and programmed values are retained 
through the loss of power.
All units have long lasting powder paint cabinets with 1000 
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
Warranty  -  All models include a one-year limited parts 
warranty on the complete unit. Compressors and electric 
heater elements carry a five-year warranty. Gas heat 
exchangers carry a 10-year parts warranty.
Gas Heat Operation - All gas heat units are built with 
two heating sections for two equal stages of capacity 
control. Each section includes a durable heat exchanger