York DJ 210 User Manual

Page of 40
261660-YTG-D-0708
Johnson Controls Unitary Products
5
with aluminized steel or optional stainless steel tubes, a 
redundant gas valve, spark ignition, power venting, an 
ignition module for 100% shut-off and all of the safety 
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating 
compartment through a hole in the base pan of the unit 
or through a knockout in the piping panel on the front of 
the unit.
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source 
and include a bank of nickel chromium elements 
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across 
the heating elements. Every element is fully protected 
against excessive current and temperature by fuses and 
two thermal limit switches.
The power supply wiring can be routed into the control 
box through a threaded pipe connection in the base pan 
of the unit or through a knockout in the wiring panel on 
the front of the unit.
BAS Controls - York’s Magnum™ series units offer fac-
tory mounted BAS controls such as Simplicity
®
 Intelli-
Comfort
, Novar, Honeywell, Johnson, York Commercial 
Comfort System (YCCS) and CPC.
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS 
- Includes a slide-in / plug-in damper assembly 
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal 
1% leakage type dampers.
The enthalpy system contains one sensor that monitors 
the outdoor air and determines when the air is cool 
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must 
be field-assembled before installing.
BAS-READY ECONOMIZER - Includes a slide-in / plug-
in damper assembly with fully modulating spring-return 
motor actuator with zero to 95-degree rotation capable of 
introducing up to 100% outdoor air with nominal 1% leak-
age type dampers.
Actuator requires 2-10 VDC input from an external 
source, such as a field-installed or factory-installed BAS 
controller. BAS-ready actuators have an adjustable auxil-
iary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, a factory-installed, dry bulb sensor deter-
mines if outdoor air temperature is low enough to provide 
free-cooling operation. (Field-installed humidity sensors 
for either outdoor air or outdoor & return air streams are 
available for single enthalpy and differential enthalpy 
configurations, respectively).
The rainhood is painted to match the basic unit and must 
be field-assembled before installing.
POWER EXHAUST - Our single economizer options are 
available with power exhaust. Whenever the outdoor air 
intake dampers are opened for free cooling, the exhaust 
fan will be energized to prevent the conditioned space 
from being over-pressurized during economizer opera-
tion. BAS-ready economizer actuators have an adjustable 
auxiliary end-switch to provide a range of damper positions 
available to energize power exhaust. For units with optional 
FIGURE 1 -  UNIT CUTAWAY
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)