York YZB018 THRU 060 User Manual

Page of 40
271457-YTG-B-0908
Johnson Controls Unitary Products
3
*  Does not achieve 13 SEER with PSC furnaces. For ratings, see technical guide or visit www.aridirectory.org/ari/unitary.html.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet 
of interconnecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.
4. Permanently mark the unit nameplate with the total system charge.  Total System Charge = Base Charge (as shipped) + adder for 
evaporator + adder for line set.
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit 
YZB1811
YZB02411
YZB03011
YZB03611
YZB04211
YZB04811
YZB06012
Required TXV
1
1TVM(901/4E1) 1TVM(902/4F1) 1TVM(903/4G1) 1TVM(904/4H1) 1TVM(904/4H1) 1TVM(905/4J1) 1TVM(906/4K1)
Factory Charge, lbs-oz
7-1
7-10
7-9
9-5
9-2
12-5
16-8
Indoor Coil
2
TXV Kit
3
  - Additional Charge, Oz
Shaded areas indicate matches that require variable speed indoor unit to meet minimum efficiently standards.
Data provided for charge adder information only.
FC/MC/PC/UC18A
901 + 0
FC/MC/PC/UC18B
901 + 0
FC/MC/PC/UC24A
902 + 5
FC/MC/PC/UC24B
902 + 5
FC/MC/PC/UC30A
902 + 5
FC/MC/PC/UC30B
902 + 5
FC/MC/PC/UC36A
903 + 5
904 + 3
FC/MC/PC/UC36B
903 + 5
904 + 3
FC/MC/PC/UC36C
903 + 5
904 + 3
FC/MC/PC/UC48C
904 + 7
FC/MC/PC/UC48D
904 + 7
FC/PC/UC60C
905 + 12
FC/MC/PC/UC60D
905 + 12
MC61D
905 + 16
FC/MC62D
906 + 0
HC18A
901 + 0
HC30A
902 + 7
903 + 5
HC36B
904 + 5
HC42C
904 + 5
HC60D
905 + 10
HD24A
901 + 9
902 + 7
HD36B
903 + 9
904 + 10
HD48C
904 + 5
HD60D
905 + 10
AHP18B
901 + 0
AHP24B
902 + 6
AHP30B
903 + 9
AHP36C
903 + 14
904 + 13
AHP42C
904 + 13
AHP/SHP48D
904 + 7
905 + 8
AHP/SHP60D
905 + 8
AV24B
901 + 3
902 + 6
AV36C
903 + 14
904 + 13
AV/SV48D
904 + 20
904 + 10
905 + 8
F*FP024H06T2A
901 + 0
F*FP024H06T2B
901 + 0
F*FP030H06T2A
902 + 3
F*FP036H06T2A
903 + 7
904 + 5
F*FP042H06T2A
904 + 7
FOOTNOTES:
1. If indoor coil comes with a factory-installed TXV, it must be removed and replaced with the required TXV.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit  2FD06700224.
3. A TXV kit must be used with these coils to obtain system performance (901, 902, 903, 904, 905 indicates 1TVM …series).