York D1EG User Manual

Page of 32
036-21411-002-A-0204
14
Unitary Products Group
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - DEE/DEG036-060 W/ DIRECT DRIVE
1
MODEL
DEE/DEG
MOTOR
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
0.20
0.30
0.40
0.50
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
036
HI
-
-
-
-
1699
825
1650
785
MED
1684
800
1631
780
1582
750
1524
720
LOW
1487
710
1464
690
1421
670
1367
650
048
HI
1996
960
1933
936
1868
910
1795
880
MED
1804
838
1765
810
1714
785
1650
765
LOW
1681
760
1640
738
1604
715
1541
695
060
HI
2400
1155
2338
1125
2274
1095
2167
1045
MED
2290
1105
2214
1065
2145
1030
2071
990
LOW
2150
1020
2100
990
2029
950
1965
910
MODEL
DEE/DEG
MOTOR
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.6
0.70
0.80
0.90
1.00
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
036
HI
1570
755
1430
725
1360
700
1280
680
1180
655
MED
1410
690
1324
650
1260
630
1185
610
1100
590
LOW
1315
620
1246
605
1185
590
1110
570
1020
545
048
HI
1722
845
1635
820
1544
790
1419
765
1300
740
MED
1589
735
1508
705
1407
675
1306
645
1195
625
LOW
1490
670
1416
645
1337
620
1230
595
1120
575
060
HI
2096
1010
1990
980
1887
945
1771
905
1629
855
MED
1990
950
1911
920
1828
885
1724
835
1604
798
LOW
1905
880
1816
838
1724
800
1644
770
1531
710
1.
Side Duct application (230/460/575 Volts)
2.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance val-
ues on applications other than gas / electric units with side duct airflows.
TABLE 12: STATIC RESISTANCES
DESCRIPTION
RESISTANCE, IWG
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
ECONOMIZER
1
 
2
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
ELECTRIC HEATERS
1
5 - 15 kW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20 - 30 kW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
BOTTOM DUCT CONNECTIONS
1
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
COOLING ONLY
3
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
1.
Deduct these resistance values from the available external static pressure shown on Tables 8, 9, 10, and 11.
2.
The pressure through the economizer is greater for 100% outdoor air than for 100% return air.  If the resistance of the return air 
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3.
Add these resistance values to the available static resistance in the respective Blower Performance Table (see Tables 8, 9, 10, 
and 11).