TABLE 15: BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA
MODEL
DEE/
DEG
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
CON.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
2
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN
MAX
RLA
LRA
036
208/230-1-60
187
253
16.7
87
2.3
7.6
30.1
45
45
208/230-3-60
187
253
13.1
110
2.3
5.3
23.9
35
35
460-3-60
414
504
6.7
54
1.4
2.6
12.4
20
20
575-3-60
3
518
630
5.1
44
1.4
2.0
9.8
15
15
048
208/230-1-60
187
253
18.7
135
2.3
8.6
42.6
60
60
208/230-3-60
187
253
11.9
130
2.3
5.2
26.3
40
40
460-3-60
414
504
6.3
64
1.4
2.6
14.3
20
20
575-3-60
3
518
630
4.9
52
1.4
2.0
11.4
15
15
060
208/230-1-60
187
253
32.1
169
2.3
8.6
51.0
80
80
208/230-3-60
187
253
19.3
123
2.3
6.0
32.4
50
50
460-3-60
414
504
10.0
62
1.4
3.0
16.9
25
25
575-3-60
3
518
630
7.9
50
1.4
2.4
13.7
20
20
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual element, time delay type.
3.
= DEE models only.