York D1EG User Manual

Page of 32
036-21411-002-A-0204
Unitary Products Group
9
TABLE 6: COOLING CAPACITIES - 4 TON (DEE / DEG048)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
95°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2000
72
64
3.9
45
39
33
27
21
-
-
60
4.2
44
38
32
26
20
-
-
67
57
3.8
55
49
43
37
31
25
19
53
4.1
53
47
41
35
29
23
17
62
54
3.8
54
54
53
47
41
35
29
50
4.0
50
50
50
44
38
32
26
57
54
3.8
54
54
54
48
42
36
30
50
4.0
50
50
50
46
40
34
28
1800
72
62
3.9
42
36
31
25
20
-
-
58
4.2
41
35
30
24
19
-
-
67
55
3.8
51
46
40
35
30
24
19
52
4.1
50
44
39
34
28
23
18
62
52
3.8
52
52
49
44
39
33
28
49
4.1
49
49
47
42
37
31
26
57
52
3.8
52
52
51
45
40
35
29
49
4.1
49
49
49
44
38
33
27
1600
72
59
3.9
38
33
29
24
19
-
-
57
4.2
38
33
28
23
18
-
-
67
54
3.8
48
43
38
33
29
24
19
52
4.2
47
42
37
32
28
23
18
62
50
3.7
50
50
46
41
36
32
27
47
4.1
47
47
45
40
35
31
26
57
50
3.7
50
50
47
42
38
33
28
47
4.1
47
47
46
41
37
32
27
1400
72
58
3.8
35
31
27
23
18
-
-
55
4.2
34
30
26
22
17
-
-
67
52
3.8
44
39
35
31
27
22
18
49
4.2
42
38
34
30
26
21
17
62
49
3.7
48
47
43
39
34
30
26
46
4.1
46
45
42
37
33
29
25
57
49
3.7
49
48
44
40
36
31
27
46
4.1
46
46
43
38
34
30
26
1200
72
57
3.8
32
29
25
21
17
-
-
53
4.2
31
28
24
20
16
-
-
67
50
3.8
40
36
32
29
25
21
17
47
4.2
38
35
31
27
23
20
16
62
48
3.7
47
44
40
36
33
29
25
45
4.1
45
42
38
34
31
27
23
57
48
3.7
48
45
41
37
34
30
26
45
4.1
45
43
39
35
32
28
24
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
115°F
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2000
72
56
4.7
42
36
30
25
19
-
-
53
5.2
41
35
29
23
17
-
-
67
50
4.6
50
45
39
33
28
22
16
47
5.1
47
44
38
32
26
20
14
62
47
4.5
47
47
47
41
35
29
23
44
5.0
44
44
44
38
32
26
20
57
47
4.5
47
47
47
44
38
32
26
44
5.0
44
44
44
42
36
30
24
1800
72
54
4.7
39
34
29
23
17
-
-
51
5.1
38
33
27
22
17
-
-
67
49
4.6
47
43
37
32
27
21
16
46
5.1
45
41
36
31
25
20
14
62
46
4.5
46
46
45
40
34
29
23
43
5.0
43
43
43
37
32
26
21
57
46
4.5
46
46
46
42
36
31
26
43
5.0
43
43
43
40
34
29
24
1600
72
53
4.7
36
31
27
22
17
-
-
49
5.1
35
30
25
21
16
-
-
67
48
4.6
45
40
35
31
26
21
16
44
5.1
43
39
34
29
24
19
15
62
44
4.6
44
44
43
38
33
29
24
41
5.0
41
41
41
36
31
26
22
57
44
4.5
44
44
44
39
34
30
25
41
5.0
41
41
41
37
32
28
23
1400
72
51
4.7
33
29
25
21
16
-
-
48
5.1
32
28
24
20
15
-
-
67
46
4.6
41
37
33
28
24
20
16
43
5.0
40
35
31
27
23
19
14
62
43
4.5
43
42
40
36
31
27
23
40
5.0
40
40
38
34
30
25
21
57
43
4.5
43
43
41
37
32
28
24
40
5.0
40
40
39
35
31
26
22
1200
72
50
4.7
30
27
23
19
16
-
-
47
5.1
30
26
22
18
15
-
-
67
44
4.6
37
33
30
26
22
19
15
42
5.0
36
32
29
25
21
18
14
62
42
4.5
42
41
37
33
29
26
22
39
5.0
39
39
35
32
28
24
21
57
42
4.5
42
41
38
34
30
27
23
39
5.0
39
39
36
33
29
25
22
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 9 or 11, multiply 
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan 
motor power input is 0.36kW. Refer to Tables 9 or 11 for the kW of the supply air blower motor.
NOMINAL RATING
ALL SENSIBLE CAPACITY