York D1EG User Manual

Page of 32
036-21411-002-A-0204
8
Unitary Products Group
TABLE 5: COOLING CAPACITIES - 3 TON (DEE / DEG036)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
95°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1500
72
55
3.4
35
31
26
22
18
-
-
51
3.7
35
30
26
21
17
-
-
67
52
3.3
47
42
38
33
29
24
20
48
3.6
45
41
36
32
28
23
19
62
42
3.2
42
42
42
37
33
28
24
39
3.5
39
39
39
34
30
25
21
57
42
3.2
42
42
42
38
33
29
24
39
3.5
39
39
39
35
30
26
21
1350
72
51
3.3
32
28
24
20
16
-
-
49
3.6
32
28
24
20
16
-
-
67
49
3.3
42
38
34
30
26
22
18
47
3.5
42
38
34
30
26
22
18
62
39
3.2
39
39
37
33
29
25
21
37
3.5
37
37
37
33
29
25
21
57
40
3.2
40
40
38
34
30
26
22
38
3.5
38
38
38
34
30
26
22
1200
72
48
3.2
28
24
21
17
14
-
-
48
3.6
29
25
22
18
15
-
-
67
46
3.3
37
34
30
27
23
19
16
46
3.5
39
36
32
38
25
21
18
62
36
3.2
36
36
33
29
26
22
19
36
3.5
36
36
35
31
28
24
21
57
37
3.2
37
37
35
31
27
24
20
37
3.4
37
37
37
33
30
26
22
1050
72
46
3.3
26
23
19
16
13
-
-
45
3.6
26
23
20
16
13
-
-
67
44
3.3
34
31
28
25
22
18
15
43
3.5
35
32
28
25
22
19
16
62
35
3.2
35
34
31
28
24
21
18
34
3.4
34
33
31
28
25
22
19
57
36
3.2
36
35
32
29
26
23
20
35
3.4
35
34
33
30
27
23
20
900
72
45
3.3
24
21
18
15
13
-
-
43
3.5
23
20
17
15
12
-
-
67
42
3.2
31
29
26
23
20
17
15
40
3.5
30
28
25
22
19
16
14
62
34
3.2
34
32
26
26
23
20
18
32
3.4
32
30
28
25
22
19
17
57
35
3.1
35
33
30
27
25
22
19
33
3.4
33
32
29
26
24
21
18
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
115°F
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
TOTAL
CAP
.1
MBH
POWER
INPUT
2
kW.
SENSIBLE CAPACITY
1
, MBH
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
CFM
WB
°F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1500
72
47
3.9
33
29
25
20
16
-
-
43
4.1
32
28
23
19
14
-
-
67
44
3.8
43
39
35
30
26
22
17
40
4.1
40
38
33
29
24
20
16
62
36
3.7
36
36
36
31
27
22
18
33
4.0
33
33
33
28
24
19
15
57
36
3.7
36
36
36
31
27
23
18
33
3.9
33
33
33
28
24
20
15
1350
72
44
3.9
30
26
22
18
14
-
-
39
4.1
28
24
20
16
12
-
-
67
42
3.8
39
36
32
28
24
20
16
37
4.0
36
33
29
25
21
17
13
62
34
3.7
34
34
33
29
25
21
17
30
4.0
30
30
30
26
22
18
14
57
34
3.7
34
34
34
30
26
22
18
30
3.9
30
30
31
27
23
19
15
1200
72
42
3.8
27
23
20
16
12
-
-
36
4.1
24
21
17
14
10
-
-
67
40
3.8
36
32
29
25
22
18
14
34
4.0
33
29
25
22
18
15
11
62
32
3.7
32
32
31
28
24
20
17
27
3.9
27
27
28
24
20
17
13
57
32
3.7
32
32
33
29
26
22
19
28
3.9
28
28
29
26
22
18
15
1050
72
40
3.8
24
21
18
15
12
-
-
35
4.1
22
19
16
13
10
-
-
67
38
3.7
32
29
26
23
19
16
13
33
4.0
30
26
23
20
17
14
11
62
30
3.7
30
30
28
25
22
19
16
27
3.9
27
27
26
22
19
16
13
57
31
3.6
31
31
30
27
24
20
17
27
3.9
27
27
27
24
21
17
14
900
72
38
3.8
22
19
16
13
11
-
-
34
4.0
20
18
15
12
9
-
-
67
36
3.7
29
26
23
20
17
15
12
32
4.0
27
24
21
18
16
13
10
62
29
3.6
29
28
26
23
20
17
15
26
3.9
26
26
24
21
18
15
13
57
30
3.6
30
29
27
24
21
19
16
26
3.9
26
26
25
22
19
17
14
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 8 or 11, multiply 
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan 
motor power input is 0.36kW. Refer to Table 8 or 11 for the kW of the supply air blower motor.
NOMINAL RATING
ALL SENSIBLE CAPACITY