York D2CG300 User Manual

Page of 24
A
B
C
D
FRONT 
4 POINT LOADS
FIG. 11- FOUR AND SIX POINT LOADS
A
E
D
B
F
C
FRONT 
6 POINT LOADS
UNIT
4 - POINT LOADS (LBS)
TOTAL
A
B
C
D
300
3,130
615
671
962
882
NOTE: These weights are with economizer, high heat, and the largest blower motor available.
UNIT
6 - POINT LOADS (LBS)
TOTAL
A
B
C
D
E
F
300
3,130
418
438
533
628
603
510
NOTE: These weights are with economizer, high heat, and the largest blower motor available.
TABLE 7 - FOUR AND SIX POINT LOADS
TABLE 8 - SUPPLY AIR BLOWER PERFORMANCE DCE300 - BOTTOM DUCT CONNECTIONS
 (
COOLING APPLICATIONS)
BLOWER
PULLEY
SPEED TURNS
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0*
1.4
5.9
4.9
1.0
7.3
6.0
0.5
8.8
7.2
-
-
-
-
-
-
1005
5.0
1.6
6.2
5.1
1.2
7.7
6.3
0.7
9.2
7.6
0.1
10.9
8.9
-
-
-
1040
4.0
1.8
6.6
5.4
1.4
8.1
6.7
0.9
9.7
8.0
0.3
11.4
9.4
-
-
-
1070
3.0
2.0
6.9
5.7
1.6
8.5
7.0
1.1
10.2
8.3
0.6
11.9
9.8
-
-
-
1100
2.0
2.1
7.3
6.0
1.8
8.9
7.3
1.3
10.6
8.7
0.8
12.4
10.2
0.2
14.3
11.7
1135
1.0
2.4
7.7
6.3
2.0
9.3
7.6
1.6
11.1
9.1
1.0
13.0
10.6
0.4
14.9
12.2
1165
0.0
2.6
8.0
6.6
2.2
9.7
8.0
1.8
11.6
9.5
1.3
13.5
11.0
0.7
15.5
12.7
1140
6.0
2.4
7.7
6.3
2.1
9.4
7.7
1.6
11.2
9.2
1.1
13.1
10.7
0.5
15.0
12.3
1180
5.0
2.7
8.2
6.7
2.3
9.9
8.1
1.9
11.8
9.7
1.4
13.7
11.2
0.8
15.8
12.9
1215
4.0
2.9
8.6
7.0
2.6
10.4
8.5
2.2
12.3
10.1
1.7
14.3
11.7
1.1
16.4
13.5
1255
3.0
3.2
9.1
7.4
2.9
11.0
9.0
2.5
12.9
10.6
2.0
15.0
12.3
1.4
17.2
14.1
1290
2.0
3.4
9.5
7.8
3.1
11.5
9.4
2.7
13.5
11.1
2.2
15.6
12.8
-
-
-
1330
1.0
3.7
10.0
8.2
3.4
12.0
9.9
3.0
14.1
11.6
2.6
16.4
13.4
-
-
-
1365
0.0
3.9
10.5
8.6
3.7
12.6
10.3
3.3
14.7
12.1
2.9
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. 
Refer to page 14 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system.  All internal unit resistances have been deducted from the total static pressure of the 
blower.
* FACTORY SETTING
12500 CFM
STANDARD DRIVE:
ACCESSORY DRIVE:
7500 CFM
8750 CFM
10000 CFM
11250 CFM
530.18-N11Y
Unitary Products Group
13