York D2CG300 User Manual

Page of 24
TABLE 11 - POWER EXHAUST PERFORMANCE
TABLE 12 - BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
DRIVE
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
BELT
(NOTCHED)
HP FRAME
EFF.
(%)
DESIG-
NATION
OUT-
SIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
PITCH
LENGTH
(IN.)
QTY.
25 TON
Stan-
dard
975/1165
15
254T
91
1LVP58B70A
7.5
6.2-
7.4
1-5/8
1B5V110
11.3
11.1 1-7/16 5VX860
86.0
1
High
Speed
Access
1140/1365
1B5V94
9.7
9.5
1-7/16 5VX840
84.0
1
1
All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream
  of any heating device.
MOTOR
SPEED
STATIC RESISTANCE OF RETURN DUCTWORK, IWG
0.2
0.3
0.4
0.5
0.6
CFM
KW
CFM
KW
CFM
KW
CFM
KW
CFM
KW
HIGH*
5250
0.83
4500
0.85
4200
0.88
3750
0.93
3000
0.99
MEDIUM
4900
0.77
3900
0.79
3500
0.82
2900
0.85
-
-
LOW
4400
0.72
3700
0.74
3000
0.78
-
-
-
-
*
Factory Setting
  Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
7500
8750
10000
11250
12500
ESP ESP ESP ESP ESP 
(IWG)
(IWG)
(IWG)
(IWG)
(IWG)
DEDUCTIONS:  (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL:
0.10
0.10
0.10
0.10
0.10
ECONOMIZER (RETURN DUCT): 0.06
0.09
0.11
0.14
0.18
18kW ELECTRIC HEAT:
0.31
0.43
0.56
0.71
0.87
36kW ELECTRIC HEAT:
0.38
0.52
0.68
0.87
1.07
54kW ELECTRIC HEAT:
0.62
0.84
1.10
1.39
1.72
72kW ELECTRIC HEAT:
0.68
0.93
1.21
1.54
1.90
ADDITIONS:  (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
HORIZONTAL (SIDE) SUPPLY DUCT:
0.31
0.26
0.27
0.31
0.41
HORIZONTAL (SIDE) RETURN DUCT:
0.05
0.05
0.05
0.05
0.05
AIRFLOW (CFM)
DESCRIPTION
TABLE 10 - STATIC RESISTANCES*
BLOWER
PULLEY
SPEED TURNS
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
ESP OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0
1.2
5.9
4.9
0.5
7.3
6.0
-
-
-
-
-
-
-
-
-
1005
5.0
1.4
6.2
5.1
0.7
7.7
6.3
-
-
-
-
-
-
-
-
-
1040
4.0
1.6
6.6
5.4
0.9
8.1
6.7
0.2
9.7
8.0
-
-
-
-
-
-
1070
3.0
1.8
6.9
5.7
1.1
8.5
7.0
0.4
10.2
8.3
-
-
-
-
-
-
1100
2.0
2.0
7.3
6.0
1.3
8.9
7.3
0.6
10.6
8.7
-
-
-
-
-
-
1135
1.0
2.2
7.7
6.3
1.6
9.3
7.6
0.8
11.1
9.1
-
-
-
-
-
-
1165
0.0
2.4
8.0
6.6
1.8
9.7
8.0
1.0
11.6
9.5
0.2
13.5
11.0
-
-
-
1140
6.0
2.2
7.7
6.3
1.6
9.4
7.7
0.9
11.2
9.2
-
-
-
-
-
-
1180
5.0
2.5
8.2
6.7
1.9
9.9
8.1
1.2
11.8
9.7
0.3
13.7
11.2
-
-
-
1215
4.0
2.7
8.6
7.0
2.1
10.4
8.5
1.4
12.3
10.1
0.6
14.3
11.7
-
-
-
1255
3.0
3.0
9.1
7.4
2.4
11.0
9.0
1.7
12.9
10.6
0.9
15.0
12.3
-
-
-
1290
2.0
3.2
9.5
7.8
2.7
11.5
9.4
2.0
13.5
11.1
1.2
15.6
12.8
-
-
-
1330
1.0
3.5
10.0
8.2
3.0
12.0
9.9
2.3
14.1
11.6
1.5
16.4
13.4
-
-
-
1365
0.0
3.7
10.5
8.6
3.2
12.6
10.3
2.6
14.7
12.1
1.8
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. 
Refer to page 14 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system.  All internal unit resistances have been deducted from the total static pressure of the 
blower.
* FACTORY SETTING
STANDARD DRIVE:
ACCESSORY DRIVE:
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
TABLE 9 - SUPPLY AIR BLOWER PERFORMANCE DCG300-BOTTOM DUCT CONNECTIONS(COOLING APPLICATIONS)
530.18-N11Y
14
Unitary Products Group