1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3.
All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4.
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub-
tract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
Physical and Electrical Data - 1 Phase
MODEL
H1RA018S06 H1RA024S06 H2RA030S06 H2RA036S06 H1RA042S06 H1RA048S06 H3RA060S06
Unit Supply Voltage
208/230 – 1 – 60
Normal Voltage Range 
1
187 to 252
Minimum Circuit Ampacity
12.5
15.6
17.5
21.5
26.1
30.1
37.3
Max. Overcurrent Device Amps 
2
20
25
30
35
40
45
60
Compressor Type 
3
Recip
Recip
Recip
Recip
Recip
Recip
Scroll
 B
Compressor Amps
Rated Load
9.6
12.1
13.6
16.1
19.8
23
28.8
Locked Rotor
54
57
73
82
97
110
160
Crankcase Heater
No
No
No
No
No
No
No
Fan Motor Amps
Rated Load
0.5
0.5
0.5
1.4
1.4
1.3
1.3
Fan Diameter Inches
18
18
18
18
18
22
22
Fan Motor
Rated HP
1/12
1/12
1/12
1/4
1/4
1/4
1/4
Nominal RPM
1,100
1,100
1,100
1,100
1,100
850
850
Nominal CFM
1,850
1,850
1,900
2,750
2,750
3,250
3,300
Coil
Face Area Sq. Ft.
8.00
8.00
9.15
9.15
12.58
15.72
15.72
Rows  Deep
1
1
1
1
1
1
1
Fin / Inches
14
14
18
18
18
18
22
Liquid Line OD
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line OD
5/8
5/8
3/4
3/4
3/4
7/8
7/8
Unit Charge (Lbs. - Oz.) 
4
3 - 6
3 - 11
3 - 14
3 - 15
5 - 4
7 - 5
6 - 2
Charge Per Foot, Oz. 
4
0.66
0.66
0.68
0.68
0.68
0.70
.070
Operating Weight Lbs.
118
123
135
137
161
176
188
Physical and Electrical Data - 3 Phase
MODEL
H1RA
036S25
H1RA
042S25
H1RA
048S25
H1RA
060S25
H1RA
076S25
H1RA
090S25
H1RA
036S25
H1RA
042S46
H1RA
048S46
H1RA
060S46
H1RA
076S46
H1RA
090S46
Unit Supply Voltage
208/230 – 3 – 60
460 - 3 - 60
Normal Voltage Range 
1
187 to 252
432 to 504
Minimum Circuit Ampacity
15.0
17.4
17.3
21.3
25.8
37.7
8.0
8.4
8.3
10.8
13.0
18.1
Max. Overcurrent Device Amps 
2
 
25
30
30
35
40
50
15
15
15
15
20
25
Compressor Type 
3
 
Recip
Recip
Recip
Scroll
B
Scroll
B
Dual
Recip
Recip
Recip
Scroll
B
Scroll
B
Dual
Compressor Amps
Rated Load
10.9
12.8
11.7
16.0
18.9
29.4
5.8
6.1
6.1
8.0
9.5
14.0
Locked Rotor
78
78
78
125
146
260
40
39
39
67
73
128
Crankcase Heater
No
No
No
No
No
Yes
No
No
No
No
No
Yes
Fan Motor Amps
Rated Load
1.4
1.4
1.3
1.3
2.2
4.6
.8
.8
.7
.8
1.2
2.3
Fan Diameter Inches
18
18
22
22
24
24
18
18
22
22
24
24
Fan Motor
Rated HP
1/4
1/4
1/4
1/4
1/3
3/4
1/4
1/4
1/5
1/4
1/3
3/4
Nominal RPM 1,100
1,100
850
850
1100
1100
1,100
1,100
850
850
1100
1100
Nominal CFM
2,750
2,750
3,250
3,450
4000
5000
2,750
2,750
3,250
3,450
4000
5000
Coil
Face Area Sq. Ft.
9.15
12.58
15.72
23.58
18.0
22.5
9.15
12.58
15.72
23.58
18.0
22.5
Rows  Deep
1
1
1
1
2
2
1
1
1
1
2
2
Fin / Inches
18
18
18
18
16
16
18
18
18
18
16
16
Liquid Line OD
3/8
3/8
3/8
3/8
1/2
1/2
3/8
3/8
3/8
3/8
1/2
1/2
Vapor Line OD
3/4
3/4
7/8
7/8
1-1/8
1-1/8
3/4
3/4
7/8
7/8
1-1/8
1-1/8
Unit Charge (Lbs. - Oz.) 
4
3 - 15
5 - 4
7 - 5
9 - 7
12-3
15-3
3 - 15
5 - 4
7 - 5
9 - 7
12-3
15-3
Charge Per Foot, Oz.
4
.68
.68
.70
.70
1.26
1.26
.68
.68
.70
.70
1.26
1.26
Operating Weight Lbs.
170
176
206
228
219
368
170
176
206
228
219
368