FIGURE 3 -  TYPICAL FIELD CONTROL WIRING DIAGRAM
TABLE 10: ADDITIONAL STATIC PRESSURE RESISTANCE 2-1/2 - 3-1/2 TON (DNA030 - 042)
1
DESCRIPTION
RESISTANCE, IWG
CFM
500
600
700
800
900
1,000
1,100
1,200
1,300
1,400
1,500
1,600
1,700
1,800
1,900
2,000
WET EVAPORATOR COIL
.01
.01
.01
.02
.03
.04
.05
.06
.07
.08
.09
.09
-
-
-
-
ECONOMIZER
2
.00
.00
.00
.01
.01
.01
.01
.02
.03
.04
.05
.06
-
-
-
-
FILTER FRAME KIT
.01
.02
.04
.06
.08
.10
.13
.16
.17
.18
.19
.20
-
-
-
-
1. Deduct these resistance values from the available external static pressure shown in Tables 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air.  If the resistance of the return air 
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 11: ADDITIONAL STATIC PRESSURE RESISTANCE 4 - 5 TON (DNA048 - 060)
1
DESCRIPTION
RESISTANCE, IWG
CFM
500
600
700
800
900
1,000
1,100
1,200
1,300
1,400
1,500
1,600
1,700
1,800
1,900
2,000
WET EVAPORATOR COIL
-
-
-
-
-
-
-
.03
.04
.05
.06
.07
.07
.08
.09
.09
ECONOMIZER
2
-
-
-
-
-
-
-
.02
.02
.03
.03
.04
.04
.04
.05
.05
FILTER FRAME KIT
-
-
-
-
-
-
-
.04
.05
.05
.06
.07
.08
.09
.10
.11
1. Deduct these resistance values from the available external static pressure shown in Table 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air.  If the resistance of the return air duct 
system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
R
G
W
R
G
C
Y
Y
W
C
PROGRAMMABLE
THERMOSTAT ONLY
**
** = Minimum wire size of 18 AWG
wire should be used for all
field installed 24 volt wire.
THERMOSTAT
UNIT TERMINAL STRIP
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
24 VOLT
TRANSFORMER