York 292443-XTG-D-0508 User Manual

Page of 28
292443-XTG-D-0508
Johnson Controls Unitary Products
15
FIGURE 4 -  TYPICAL FIELD POWER WIRING DIAGRAM
CONTACTOR
FIELD-SUPPLIED
DISCONNECT
SINGLE
PHASE
POWER
SUPPLY
GROUND
LUG
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
CONTACTOR
GROUND
LUG
FIELD-SUPPLIED
DISCONNECT
THREE
PHASE
POWER
SUPPLY
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
TABLE 12: ELECTRICAL DATA
MODEL
DNA
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
030
208/230-1-60
187
253
14.7
73
1.1
2.2
21.7
30
30
0.96
40
036
208/230-1-60
187
253
17.3
94
1.1
3.5
26.2
35
35
0.96
40
036
208/230-3-60
187
253
10.9
78
1.1
3.5
18.2
25
25
0.96
75
036
460-3-60
414
504
5.8
40
0.6
1.8
9.6
15
15
0.96
75
042
208/230-1-60
187
253
15.4
86
1.1
3.5
23.9
30
30
0.96
40
042
208/230-3-60
187
253
11.5
88
1.1
3.5
19
25
25
0.96
75
042
460-3-60
414
504
5.8
42
0.6
1.8
9.7
15
15
0.96
75
048
208/230-1-60
187
253
24.4
140
1.3
7
38.8
50
50
0.96
40
048
208/230-3-60
187
253
14.1
105
1.3
7
25.9
35
35
0.96
75
048
460-3-60
414
504
7.1
55
0.7
3.5
13.1
20
20
0.96
75
060
208/230-1-60
187
253
28.9
175
1.3
7
44.4
60
60
0.96
40
060
208/230-3-60
187
253
15.5
125
1.3
7
29.5
40
40
0.96
75
060
460-3-60
414
504
8.9
66.5
0.7
3.5
15.4
20
20
0.96
75
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.