York CH060 User Manual

Page of 28
036-21217-001-B-1203
Unitary Products Group
3
DESCRIPTION
These units are completely assembled, piped, wired, charged 
and tested at the factory and are shipped ready for immediate 
installation. Only the power supply wiring, the thermostat wir-
ing, the condenser water piping, the condensate drain piping 
and the ductwork are required to complete the installation.
Units include a one-year limited warranty on all replacement 
parts and a five-year limited warranty on each compressor.
APPLICATION FLEXIBILITY
These ìcooling onlyî units can be applied with:
1. Cooling towers.
2. Well or surface water providing the temperature and the 
GPM of the water meet the application limitations of the 
unit.
3. Brackish or salt water and a secondary heat exchanger.
They can be installed:
1. Within the conditioned space as ìfree standingî units 
without any ductwork. Supply air plenum and return air 
grille accessories are available for these freestanding 
applications.
2. In an equipment room with both supply and return air 
ductwork
GENERAL
Horizontal (CH) units are designed for suspended  mounting. 
HWC models are shipped with ëstraight-throughí evaporator 
fan discharge as standard. Airflow orientation is field convert-
ible to side discharge. Vertical (CU) units are designed for 
free-standing floor mounting. All units are completely factory 
wired and pre-piped. Water supply, water outlet, and conden-
sate drain connections are via female pipe thread fittings.
All models 5 -25 tons ship as factory-charged unitized pack-
ages. The 5 -15 ton units may be field split between the evap-
orator /compressor section and the upper blower section; 
installation is possible through standard height doorways and 
elevators. All packages are designed for free-standing floor 
mounting. All models are shipped with vertical evaporator fan 
discharge as standard. Units are completely factory wired 
and piped. Dual circuit models feature internally manifolded 
condensers. 
CABINET
All cabinets are completely constructed of 18 Ga. corrosion 
resistant "Galvalume" coated steel. The entire unit interior 
(both evaporator and condensing section) is insulated with 
1/2" thick, 2 lbs. density insulation. Service panels are 
equipped with lifting handles for ease of removal and han-
dling. Duct flanges for return air intake and evaporator dis-
charge are provided with the unit, for field installation. Duct 
flange on CU240 evaporator return is incorporated into the fil-
ter frame. 
REFRIGERATION CIRCUITS 
All models utilize "Scroll" type hermetic compressors. Com-
pressors are mounted on rubber isolators to minimize vibra-
tion transmission. Internal overload protection is provided. 
External high pressure and low pressure cutout switches are 
included in each compressor control circuit. The 5 ton units 
have a single refrigeration circuit. The 8 -20 ton units feature 
two independent refrigeration circuits. Each refrigeration cir-
cuit includes an adjustable thermal expansion valve (with 
external equalizer), liquid line filter drier, sight glass/moisture 
indicator, and service gauge ports. 
The evaporator coils are constructed of internally enhanced 
copper tubes mechanically bonded to rippled aluminum plate 
fins. The evaporator coil is employed in a draw-through con-
figuration, and features inter-laced circuiting.  Large evapora-
tor coil face area minimizes potential water blow-off.
The high-efficiency tube-in-tube condensers feature a convo-
luted inner tube design for optimum performance. Standard 
models feature a copper inner tube surrounded by a steel 
outer tube, and carry a 400 psig working pressure rating.
INDOOR FANS
Forward curved, double inlet and double width centrifugal 
blowers are used for evaporator air movement. Large diame-
ter wheels are employed to provide required airflow perfor-
mance at minimum rpm and noise levels. Blower wheels are 
fabricated of galvanized steel. Blowers employ solid steel 
shafts, supported in permanently lubricated ball bearings. All 
blowers are belt driven. Variable-pitch motor sheaves allow 
for field adjustment of blower rpm. 
ELECTRICAL/CONTROLS
All units are completely factory wired with all necessary con-
trols. Manual reset protection is provided on  evaporator 
blower motors. A manual reset circuit is also provided on 
each compressor control circuit in the event of high/low pres-
sure cutout.  A 24 volt control circuit, with oversize trans-
former, is provided for field connection. Units are designed to 
operate with conventional thermostat control interface. 
FILTERS
All models are shipped with 2 inch thick medium-efficiency 
throwaway filters factory installed. Filters are accessible from 
either front or right side on 5-15 ton models. The CU240 filter 
rack is external to the cabinet (shipped loose).