York CH060 User Manual

Page of 28
036-21217-001-B-1203
4
Unitary Products Group
NOTE: Cooling performance is rated at 80∞F dry bulb 67∞F wet bulb entering air temperature, CFM listed, 85∞F entering 
95∞F leaving water temperature, and water flow rate listed. Gross capacity does not include the effect of evapora-
tor fan motor heat.
TABLE 1: GENERAL DATA - CH060-120 5-10 TON HORIZONTAL MODELS
Model
CH060
CH096
CH120
Nominal Cooling(Ton)
5
8
10
Cooling Performance
Gross Cooling Capacity(Btuh)
64100
101800
126000
Design CFM
2000
3200
4000
EER
13.3
13.4
12.0
Compressor-Type
Scroll
Number Used
1
2
2
Evaporator Coil-Type
Copper Tubes, Aluminum Fins
Face Area(sq ft)
5.28
9.17
9.17
Rows/FPI
3/13
3/13
3/13
Condenser-Type
Coaxial
Number Used/Tons Capacity
1/5
2/4
2/5
Nominal Water flow rate (gpm)
15
24
30
Condenser Water Connections
1" FPT
1-1/4" FPT
1-1/4" FPT
Evaporator Fan-Type
Centrifugal, Forward Curved
Number Used
1
2
2
Diameter x Width (in)
10x10
10x8
10x8
Drive
Adjustable Belt
Motor HP (Standard/Oversize)
1/NA
1.5/2
2/3
Filters
Number Used-Size(in)
2-20x20x2
2-20x25x2
1-20x20x2
2-20x25x2
1-20x20x2
Condensate Drain Connection
3/4FPT
Weight
460
710
760