InRoom Precision AC Tech Data Manual
Air Cooled (DX) System - 50Hz
Net Cooling Capacity
PA211
Cabinet Size 1
PA311
Cabinet Size 2
PA452
Cabinet Size 3
PA612
Cabinet Size 4
PA862
Cabinet Size 5
26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH
Total - kW (BTU/hr)
18.9 (64,505)
28.4 (96,900)
41.8 (142,595)
53.9 (184,110)
80.6 (275,215)
Sensible - kW (BTU/hr)
18.9 (64,505)
28.4 (96,900)
41.8 (142,595)
53.9 (184,110)
73.9 (252,225)
23.9°C DB, 16.9°C WB (75°F DB, 62.5°F WB) 50% RH
Total - kW (BTU/hr)
17.7 (60,325)
26.1 (89,110)
38.7 (132,240)
49.7 (169,575)
73.2 (249,945)
Sensible - kW (BTU/hr) *
17.7 (60,325)
26.1 (89,110)
38.7 (132,240)
49.7 (169,575)
73.2 (249,945)
23.9°C DB, 16.1°C WB (75°F DB, 61°F WB) 45% RH
Total - kW (BTU/hr)
17.7 (60,325)
26.1 (89,110)
38.7 (132,240)
49.7 (169,575)
73.4 (250,610)
Sensible - kW (BTU/hr)
17.7 (60,325)
26.1 (89,110)
38.7 (132,240)
49.7 (169,575)
73.4 (250,610)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB) 50% RH
Total - kW (BTU/hr)
16.9 (57,665)
25.1 (85,595)
36.9 (126,065)
47.7 (162,640)
70.2 (239,590)
Sensible - kW (BTU/hr)
16.9 (57,665)
25.1 (85,595)
36.9 (126,065)
47.7 (162,640)
70.2 (239,590)
22.2°C DB, 14.8°C WB (72°F DB, 58.6°F WB) 45% RH
Total - kW (BTU/hr)
16.9 (57,665)
25.1 (85,595)
36.9 (126,065)
47.7 (162,640)
70.2 (239,590)
Sensible - kW (BTU/hr)
16.9 (57,665)
25.1 (85,595)
36.9 (126,065)
47.7 (162,640)
70.2 (239,590)
21.1°C DB, 14.0°C WB (70°F DB, 58.5°F WB) 50% RH
Total - kW (BTU/hr)
16.9 (57,665)
24.2 (82,650)
35.7 (121,885)
45.9 (156,560)
68.0 (232,085)
Sensible - kW (BTU/hr)
16.9 (57,665)
24.2 (82,650)
35.7 (121,885)
45.9 (156,560)
68.0 (232,085)
21.1°C DB, 14.0°C WB (70°F DB, 57.2°F WB) 45% RH
Total - kW (BTU/hr)
16.9 (57,665)
24.2 (82,650)
35.7 (121,885)
45.9 (156,560)
68.0 (232,085)
Sensible - kW (BTU/hr)
16.9 (57,665)
24.2 (82,650)
35.7 (121,885)
45.9 (156,560)
68.0 (232,085)
Condensing temperature for all above conditions: 52°C (125°F)
Refrigerant type for all models: 407C
Refrigerant Charge per Circuit - kg (lbs)
2.8 (6.17)
3.9 (8.6)
4.4 (9.7)
3.9 (8.6)
4.6 (10.1)
Compressor Information – COP** (ARI*** Conditions): 7.2°C (45°F) Evaporating, 54°C (130°F) Condensing
Number  of  compressors
1
1
2
2
2
COP
3.1
3.1
3.0
3.1
3.0
Evaporator Coil
Face Area - m² (ft²)
0.77 (8.32)
1.17 (12.63)
1.46 (15.72)
1.86 (20.02)
2.22 (23.90)
Rows  Deep
4
4
4
4
5
Face Velocity - m/min (ft/min)
125 (410)
104 (342)
117 (383)
124 (407)
141 (461)
* Nominal Rating Point
** Coefficient of Performance 
*** Air Conditioning and Refrigeration Institute