APC ACPCW40-150 User Manual

Page of 92
49
InRoom Precision AC Tech Data Manual
MultiCool - Air Cooled (DX) with CW - 50Hz
Operational Mode: Air (DX)
Net Cooling Capacity 
PACW211
Cabinet Size 1
PACW311
Cabinet Size 2
PACW452
Cabinet Size 3
PACW612
Cabinet Size 4
PACW862
Cabinet Size 5
26.7°C DB, 19.4°C WB (80°F DB, 67°F WB) 50% RH
Total - kW (BTU/hr)
19.5 (66,405)
28.2 (95,235)
41.3 (140,980) 53.3 (181,830) 79.6 (271,605)
Sensible - kW (BTU/hr)
19.5 (66,405)
28.2 (95,235)
41.3 (140,980) 53.3 (181,830) 72.8 (248,615)
23.9°C DB, 16.9°C WB (75°F DB, 62.5°F WB) 50% RH
Total - kW (BTU/hr)
17.4 (59,280)
25.9 (88,540)
38.3 (130,625) 49.1 (167,580) 72.2 (246,335)
Sensible - kW (BTU/hr) *
17.4 (59,280)
25.9 (88,540)
38.3 (130,625) 49.1 (167,580) 72.2 (246,335)
23.9°C DB, 16.1°C WB (75°F DB, 61°F WB) 45% RH
Total - kW (BTU/hr)
17.4 (59,280)
25.9 (89,540)
38.3 (130,625) 49.1 (167,580) 72.4 (247,000)
Sensible - kW (BTU/hr)
17.4 (59,280)
25.9 (89,540)
38.3 (130,625) 49.1 (167,580) 72.4 (247,000)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB) 50% RH
Total - kW (BTU/hr)
16.6 (56,715)
24.9 (84,930)
36.5 (124,450) 46.6 (159,125) 69.1 (235,980)
Sensible - kW (BTU/hr)
16.6 (56,715)
24.9 (84,930)
36.5 (124,450) 46.6 (159,125) 69.1 (235,980)
22.2°C DB, 14.8°C WB (72°F DB, 58.6°F WB) 45% RH
Total - kW (BTU/hr)
16.6 (56,715)
24.9 (84,930)
36.5 (124,450) 46.6 (159,125) 69.1 (235,980)
Sensible - kW (BTU/hr)
16.6 (56,715)
24.9 (84,930)
36.5 (124,450) 46.6 (159,125) 69.1 (235,980)
21.1°C DB, 14.0°C WB (70°F DB, 58.5°F WB) 50% RH
Total - kW (BTU/hr)
16.1 (55,100)
24.0 (81,985)
35.2 (124,450) 45.5 (155,230) 67.0 (228,570)
Sensible - kW (BTU/hr)
16.1 (55,100)
24.0 (81,985)
35.2 (124,450) 45.5 (155,230) 67.0 (228,570)
21.1°C DB, 14.0°C WB (70°F DB, 57.2°F WB) 45% RH
Total - kW (BTU/hr)
16.1 (55,100)
24.0 (81,985)
35.2 (124,450) 45.5 (155,230) 67.0 (228,570)
Sensible - kW (BTU/hr)
16.1 (55,100)
24.0 (81,985)
35.2 (124,450) 45.5 (155,230) 67.0 (228,570)
Condensing temperature for above conditions: 48.8°C (120° F)
Refrigerant type for all models: 407C
Refrigerant Charge per Circuit - kg (lbs)
2.8 (6.17)
3.9 (8.6)
4.4 (9.7)
3.9 (8.6)
4.6 (10.1)
Compressor Information – COP** (ARI*** Conditions): 7.2°C (45°F) Evaporating, 54°C (130°F) Condensing
Number  of  compressors
1
1
2
2
2
COP
3.0
3.1
3.0
3.1
3.0
Connection Sizes
Liquid Line OD - mm (in)
12 (1/2)
16 (5/8)
16 (5/8)
16 (5/8)
16 (5/8)
Discharge Line OD - mm (in)
16 (5/8)
22 (7/8)
22 (7/8)
22 (7/8)
22 (7/8)
Evaporator Coil
Face Area - m² (ft²)
0.77 (8.32)
1.17 (12.63)
1.46 (15.72)
1.86 (20.02)
2.22 (23.90)
Rows  Deep
4
4
4
4
4
Face Velocity - m/min (ft/min)
125 (410)
104 (342)
117 (383)
124 (407)
141 (461)
* Nominal Rating Point
** Coefficient of Performance 
*** Air Conditioning and Refrigeration Institute