APC ACPA4000 User Manual
11
NetworkAIR ACPA4000
Drain Line
The equipment contains an on-board condensate pump for automatic condensate removal.The equipment
ships with 15.24 m (50 ft) of hose and a quick-connect fitting for removing condensate. You can attach a
different hose to the equipment if you follow these requirements:
ships with 15.24 m (50 ft) of hose and a quick-connect fitting for removing condensate. You can attach a
different hose to the equipment if you follow these requirements:
• You must use a 6-mm (1/4-in) outside diameter (OD), clear, polyurethane hose.
• The hose length must not exceed 15.24 m (50 ft), and 4.88 m (16 ft) vertical maximum.
• You must cut off all excess drain line and avoid kinking or pinching the drain line.
• The hose length must not exceed 15.24 m (50 ft), and 4.88 m (16 ft) vertical maximum.
• You must cut off all excess drain line and avoid kinking or pinching the drain line.
Connect the fitting to the
drain line.
drain line.
1. Insert the drain hose
through the capture nut
.
2. Push the drain hose
over the barbs at the rear
of the quick-connect
fitting
of the quick-connect
fitting
.
3. Screw the capture nut
onto the quick-connect
fitting
fitting
.
Attach the drain line.
Attach
the connector end of the hose to the drain line
connector on the rear of the equipment and run
the hose to a drain.
connector on the rear of the equipment and run
the hose to a drain.
Detach the drain line.
Press the quick-
release button on the top of the drain line
connector and remove the hose.
connector and remove the hose.
na
26
5
8a
na0
31
9
a
Note: The equipment does not drain
unless the drain line is installed.
unless the drain line is installed.