Emerson Series 3000 MVD User Manual

Page of 348
184
Micro Motion
®
 Series 3000 MVD Transmitters and Controllers
Measurement Performance
Specification uncertainty limit
The specification uncertainty limit defines the acceptable degree of variation from factory results, 
expressed as a percentage. Variation inside the limit is reported as Pass. Variation outside the limit is 
reported as Fail or Caution. 
In Smart Meter Verification, the specification uncertainty limit is set at the factory and cannot 
be configured.
In the original version of meter verification, the specification uncertainty limit is configurable. 
However, Micro Motion suggests using the default value. Contact Micro Motion Customer 
Service before changing the specification uncertainty limit.
21.3.2
Running the meter verification test, original version
To run a meter verification test:
With ProLink II, see Figure 21-1
With the display, see Figure 21-2
Note: If you start a meter verification test from ProLink II, the transmitter display shows the following 
message:
SENSOR
VERFY/x
%