Removing and Replacing the Gas 
Control Valve/Thermostat
IMPORTANT: The gas control valve/thermostat is a standard 
valve with wire leads that connect to a thermal switch. 
Removing the Gas Valve:
1.  On the gas control valve/thermostat turn the temperature 
dial counterclockwise to its lowest setting. Depress the 
dial stop and turn the gas control knob clockwise to the 
“OFF” position (Figure 19).
2.  Turn off the gas at the manual shut-off valve on the gas 
supply pipe (Figure 3).
3.  Drain the water heater. Refer to the section of Draining 
and Flushing and follow the procedure.
4.  Disconnect the igniter wire from the igniter button. 
Remove the igniter button by depressing front and rear 
holding tabs and lift. Remove igniter bracket. Disconnect 
the thermocouple (right-hand threads), pilot tube, two 
wire leads at the thermal switch, and manifold tube at 
the gas control valve/thermostat (Figure 22). NOTE: 
L.P. gas systems use reverse (left-hand) threads on the 
manifold tube.
5.  Refer to “Gas Piping” (Figure 3) and disconnect the 
ground joint union in the gas piping. Disconnect the 
remaining pipe from the gas control valve/thermostat.
6.  To remove the gas valve, thread a correctly sized 
Flame Lock
 Safety System Operational Checklist
TROUBLESHOOTING CHART
pipe into the inlet and use it to turn the gas valve 
(counterclockwise.) Do not use pipe wrench or 
equivalent to grip body.  Damage may result, causing 
leaks. Do not insert any sharp objects into the inlet or 
outlet connections. Damage to the gas valve may result.
Replacing the Gas Valve:
To replace the gas control valve/thermostat, reassemble in 
reverse order.  This water heater has a resettable thermal 
switch installed. DO NOT attempt to disable or modify this 
feature in any way. When replacing the gas valve, thread a 
correctly sized pipe into the inlet and use it to turn the gas 
valve (clockwise.) DO NOT OVER TIGHTEN, damage may 
result. 
• 
Be sure to use approved Teflon
®
 tape or pipe joint 
compound on the gas piping connections and fitting on 
the back of the gas control valve that screws into tank.
• 
Be sure to remove the pilot ferrule nut from the new gas 
control valve/thermostat.
• 
Turn the gas supply on and check for leaks. Test all 
connections by brushing on an approved noncorrosive 
leak-detection solution. Bubbles will show a leak. 
Correct any leak found.
• 
Be sure tank is completely filled with water before 
lighting and activating the water heater. Follow the 
Lighting Instructions.
• 
If additional information is required, contact the Service 
Department at: 1-877-817-6750.
TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
5.  No leaks at pilot and manifold connection.
6.  Manifold door screws securely tightened. 
7.  Depress the button on the thermal switch.          
       
1.  Manifold gasket properly sealed.
2.  Viewport not damaged or cracked.
3.  Flame-trap free of debris and undamaged.
4.  Two piece wire connector properly installed.
PROBLEM
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
BURNER WILL NOT IGNITE
1.  Pilot not lit
2.  Thermostat set too low
3. No 
gas
4.  Dirt in the gas lines
5. Pilot 
line 
clogged
6.  Main burner line clogged
7. Non-functioning 
thermocouple
8. Non-functioning 
thermostat
9.  Heater installed in a confined area
1. Light 
pilot
2.  Turn temp. dial to desired temperature
3.  Check with gas utility company
4.  Notify utility-install trap in gas line
5.  Clean, locate source and correct
6.  Clean, locate source and correct
7. Replace 
thermocouple
8. Replace 
thermostat
9.  Provide fresh air ventilation
SMELLY WATER
1.  Sulfides in the water
1.  Replace the anode with a special anode
BURNER FLAME YELLOW-
LAZY
1.  Insufficient secondary air
2. Low 
gas 
pressure
3. Flue 
clogged
4.  Main burner line clogged
5.  Heater installed in a confined area
6.  Obstruction in main burner orifice
1.  Provide ventilation to water heater
2.  Check with gas utility company
3.  Clean, locate source and correct
4.  Clean, locate source and correct
5.  Proper fresh air ventilation
6.  Clean or replace orifice
PILOT WILL NOT LIGHT OR 
REMAIN LIT
1. Non-functioning 
igniter
2.  The thermal switch tripped
3. Thermocouple 
connection 
loose
4.  Air in gas line
5. Low 
gas 
pressure
6. No 
gas
7.  Dirt in gas lines
8. Cold 
drafts
9.  Thermostat ECO switch open
10.  Pilot line or orifice clogged
11. Non-functioning thermocouple
12.  Air for combustion obstructed
13.  Flammable vapors incident, Flame Lock
 
function utilized
1.  Replace igniter pilot assembly
2.  See Pilot Light Troubleshooting Flowchart
section
3.  Finger tighten; then 1/4 turn with wrench
4.  Bleed the air from the gas line
5.  Check with gas utility company
6.  Check with gas utility company
7.  Notify utility-install dirt trap in gas line
8.  Locate source and correct
9. Replace 
thermostat
10.  Clean, locate source and correct
11. Replace thermocouple
12.  See maintenance section for inspection and   
cleaning of flame trap 
13.  Replace water heater, eliminate flammable 
vapors source. Call 1-877-817-6750