HONEYWELL
 
Copyright © 2007 Honeywell GmbH  All Rights Reserved 
  
EN1B-0203GE51 R0507C 
 
R7426A,B,C 
TEMPERATURE CONTROLLER 
WITH AND WITHOUT REAL-TIME CLOCK 
INSTALLATION & START-UP INSTRUCTIONS 
 
 
Fig. 1. Temperature Controller 
 
Contents 
General................................................................................ 1
 
Before Installation Note ....................................................... 1
 
Mounting.............................................................................. 1
 
Wiring .................................................................................. 2
 
Power Supply and Grounding.............................................. 2
 
Configuration and Control Parameters ................................ 3
 
Configuration Settings ......................................................... 6
 
Parameter Settings and Adjustment .................................... 8
 
Operating Overview............................................................11
 
Notes (with RTC, only)....................................................... 19
 
 
 
GENERAL 
This document provides instructions and procedures for 
installing and starting up the Micronik 200 R7426A,B,C 
controllers. No special tools are required for mounting and 
installation. The user interface and liquid-crystal display allow 
accurate and easy parameter setting and output adjustment. 
 
BEFORE INSTALLATION NOTE 
•  Visually inspect equipment for shipping damage. 
Report any damage to the appropriate Honeywell 
representative. 
•  Refer to job drawings for specific installation 
information and mounting location. 
•  Verify the controllers will be adequately separated 
from the main power supply, relays, or other equip-
ment which can possibly generate electromagnetic 
interference. 
•  Verify that the ambient temperature and the humidity 
at the controllers will not exceed 0...50
°C (32...122°F) 
and 5 to 95% rh. 
•  Use shielded wiring in areas with high EMI. 
•  All wiring should be separated from power lines by at 
least 150 mm (6’’). 
•  Do not install controllers near frequency converters 
or other high-frequency sources. 
 
MOUNTING 
The controllers can be mounted in an electric cabinet or other 
suitable enclosure. They are suitable for back panel, DIN rail, 
wall, or front panel mounting. The corresponding mounting 
sequence, as well as dimensions and panel cut-out, are 
illustrated in the mounting instruction sheet EN1B-0202GE51 
supplied with the controllers. 
If the compensation sensor signal (T3) is received from 
another controller (parallel connection of compensation 
sensor inputs), the jumper W303 has to be cut before 
mounting the controller (see Fig. 2). This disconnects the 
sensor from the internal power supply. 
MicroniK 200