Honeywell SP970A User Manual

Page of 8
SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS 
SP970C and D: Four Port Switches 
These minimum position devices have a separate dead 
ended chamber connected to port 3 to receive an 
external signal. When the external signal is less than the 
spring load, the signal has no effect and functions similar 
PILOT 
CHAMBER 
PILOT 
BRANCH 
VENT 
MAIN 
SP970C,D 
A. BUILDING TO MINIMUM SETTING 
SP970C,D 
PILOT 
BRANCH 
VENT 
MAIN 
B. BALANCED AT MINIMUM SETTING 
to the SP970A, B as a pressure regulator. When the 
external signal is greater than the spring load, the spring 
load is isolated and the device duplicates the input 
signal. See Fig. 7. 
SP970C,D 
DISC 
PILOT 
BRANCH 
VENT 
MAIN 
C. PILOT BUILDING BRANCH ABOVE
 MINIMUM SETTING 
SP970C,D 
PILOT 
BRANCH 
VENT 
MAIN 
D. BALANCED AGAINST PILOT 
C4300 
Fig. 7. SP970C and D operation. 
Application 
Fig. 8A shows a typical manual position application using 
the three port SP970A, B. This control system manually 
positions a damper between OPEN and CLOSED. 
Turning the setpoint knob clockwise increases the 
branchline pressure to the damper actuator and opens 
the damper. Turning the position knob counterclockwise 
decreases the branchline pressure and closes the 
damper. 
The three port SP970A, B is also used with a controller 
for automatic damper positioning with minimum position. 
See Fig. 8B. When the external signal is less than the 
knob setting, the spring maintains the branchline 
pressure as previously described. When the external 
signal rises above the knob setting, air from the signal 
flows directly to the branch. During steady state 
conditions, the external automatic controller must be 
capable of exhausting the air flowing through the exhaust 
(pilot) port 4. 
Fig. 8C shows a typical four port SP970C, D application. 
The minimum position switch keeps the pneumatic 
actuator at a minimum position until the thermostat 
pressure is greater than the minimum position valve. The 
thermostat then controls the actuator. 
DAMPER 
DAMPER 
1  2 
DAMPER 
ACTUATOR 
ACTUATOR 
ACTUATOR 
SP970C OR D 
INSERTION 
THERMOSTAT 
3
BRANCH 
BRANCH 
EXH 
SP970A OR B 
CONTROLLER 
B. MINIMUM POSITION
C. MINIMUM POSITION 
APPLICATION WITH 
APPLICATION 
CONTROLLER INPUT 
WITH THERMOSTAT 
C8279 
Fig. 8. Typical SP970 application. 
BRANCH 
EXH 
SP970A OR B 
A. MANUAL POSITION 
APPLICATION 
Automation and Control Solutions 
Honeywell 
Honeywell Limited-Honeywell Limitée 
1985 Douglas Drive North 
35 Dynamic Drive 
Golden Valley, MN  55422 
Scarborough, Ontario 
M1V 4Z9 
Printed in U.S.A. on recycled
95-7237EF    J.H. Rev. 2-02 
customer.honeywell.com 
paper containing at least 10% 
post-consumer paper fibers.