Honeywell TB7220 User Manual

Page of 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
13
63-2635—03
INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND TESTS (TABLE 6)
Use the Installer System Test to test the heating, cooling and 
fan. Refer to the latter portion of Table 6.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during 
Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling and 
fan. The setting chosen for System Type (ISU 0170) 
can prevent some System Test Numbers from 
appearing.
NOTE: Unless otherwise noted, setup items are accessible 
through only the Installer setup and not the User 
setup.
Table 6. Installer Setup Menu.
Installer
 Setup 
Number
Installer Setup 
Name
Default 
Setting
All Settings
Notes
0120
a
Date (Year Upper)
20
20—20xx
21—21xx
Available year range: 2001 - 2178
0130
a
Date (Year Lower)
04
00-99
Available year range: 2001 - 2178
0140
a
Date (Month)
6
1-12
0150
a
Date (Day)
15
1-31 (Month Dependent)
0160
a
Schedule Options
4
0—Non-Programmable
4—Programmable
0170
System Selection
8
1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP
0175
TOD/Economizer 
output
0
0—Unused
1—TOD
2—Economizer
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and deenergizes 
A during Unoccupied.
0180
Heat Fan Operation 0
0—Fossil
1—Electric
Only shown for conventional system with heat stages and 
fan capability selected. If heat pump is selected, fan 
defaults to electric.
0185
Pre-occupancy 
Purge Duration
0
0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule programmable.
Pre-occupancy purge enabled by nonzero duration (and 
sends economizer to minimum position).
0190
Reversing Valve O/B 0
0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown with heat pump system selected.
0220
Cycles Per Hour 
(CPH) for first stage 
compressor
3
1-6
Only shown for system with cool stages. Selection in this 
stage changes default CPH of second stage cool.
0230
CPH for second 
stage compressor
3
1-6
Only shown if two stages of cool selected.
0240
CPH for first stage 
conventional heat
5
1-12
Only shown if system is conventional with heat stages.
Selection in this stage changes default CPH of second 
stage heat.
0250
CPH for second 
stage conventional 
heat
5
1-12
Only shown with at least two stages conventional heat or 
2H/1C heat pump selected.
a
Setting available for modification in both the Installer and User setup modes.