Honeywell TB7220 User Manual

Page of 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
63-2635—03
14
0260
CPH for third Stage 
Heat
9
1-12
Only shown if 3H/2C heat pump is selected.
0270
CPH for Auxiliary 
Heat
9
1-12
Only shown if multi-stage heat pump is selected (heat 
pump with more heat than cool stages).
0280
Continuous 
Backlight
0
0—No
1—Yes
Always shown. If AC power not present the option is 
overridden and normal backlight operation occurs.
0300
Changeover
1
0—Manual
1—Auto
Only shown if system has both heat and cool stages.
0310
Deadband
3°F 
(2°C)
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover Selected
0320
a
Temperature 
Indication Scale
0
0—°F
1—°C
0330
a
Daylight Saving
1
0—Disabled
1—Enabled (US)
0340
Remote 
Temperature Sensor
0
0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
Averaging would not include on-board sensor. It is 
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing 
compressor lockout while displaying temperature).
0350
Heat Pump 
Compressor Lockout
0
0—None
15(-9.5)—15°F(-9.5°C)
20(-6.5)—20°F(-6.5°C)
25(-4.0)—25°F(-4.0°C)
30(-1.0)—30°F(-1.0°C)
35(1.5)—35°F(1.5°C)
40(4.5)—40°F(4.5°C)
45(7.0)—45°F(7.0°C)
Only shown for heat pump systems with more heat stages 
than cool selected and remote sensor selection is outdoor 
for control.
Must enforce a dead band between this and Auxiliary 
Lockout
0360
Heat Pump Auxiliary 
Lockout
0
0—None
40(4.5)—40°F(4.5°C)
45(7.0)—45°F(7.0°C)
50(10.0)—50°F(10.0°C)
55(13.0)—55°F(13.0°C)
60(15.5)—60°F(15.5°C)
Only shown for heat pump systems with more heat stages 
than cool selected and remote sensor selection is outdoor 
for control.
Must enforce a dead band between this and Heat Pump 
Compressor Lockout.
0535
Temporary Occupied 
Duration Limit
3
0—no duration
1—one hour
2—two hours
3—three hours
4—four hours
0 means no limit
0540
a
Number of Periods
4
2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the “Cancel 
Period” option does not appear on the display.
0580
Minimum 
Compressor Off 
Time
5
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Only shown if system has cool stages.
0600
Heat Temperature 
Range Stops
90
40 to 90°F (4 to 32°C)
Only shown if system has heat stages.
0610
Cool Temperature 
Range Stops
50
50 to 99°F (10 to 37°C)
Only shown if system has cool stages.
Table 6. Installer Setup Menu. (Continued)
Installer
 Setup 
Number
Installer Setup 
Name
Default 
Setting
All Settings
Notes
a
Setting available for modification in both the Installer and User setup modes.