Honeywell TB7220 User Manual

Page of 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
19
63-2635—03
Partially Locked Screen
When partially locked:
— Pressing a locked key prompts the screen to indicate 
SCREEN LOCKED for five to seven seconds.
— Pressing an unlocked key with SCREEN LOCKED active 
removes SCREEN LOCKED from the display.
PARTIAL LOCKOUT 1
This mode locks all keys except HOLIDAY, OVERRIDE, and 
temperature Up/Down arrows:
— User can change the temperature setpoint, but cannot 
change schedule settings.
— The temporary temperature change lasts until next 
scheduled period. The screen displays that time.
— User can change the temperature setpoint, but cannot 
change schedule settings.
— Pressing HOLIDAY sets the temperature to the Unoccupied 
setting for the selected period of time. The next Occupied 
period switches back to the program settings.
— Pressing OVERRIDE sets the temperature to the Occupied 
setting for the selected period of time. The next Unoccupied 
period switches back to the program settings.
— To cancel the temperature override and follow the 
programmed schedule, press CANCEL.
— To unlock the screen, see Advanced Settings section.
PARTIAL LOCKOUT 2
This mode locks all keys except HOLIDAY and OVERRIDE:
— Pressing HOLIDAY sets the temperature to the Unoccupied 
setting for the selected period of time. The next Occupied 
period switches back to the program settings.
— Pressing OVERRIDE sets the temperature to the Occupied 
setting for the selected period of time. The next Unoccupied 
period switches back to the program settings.
— To cancel the temperature override and follow the 
programmed schedule, press CANCEL.
— To unlock the screen, see Advanced Settings section.
Temperature Recovery
The thermostat is equipped with a feature to eliminate 
guesswork when setting a schedule. That is, the user need not 
know the amount of time for the HVAC system to bring the 
space to temperature (without overshoot) prior to the 
scheduled time.The thermostat manages that automatically.
Simply set the program schedule to the desired time to have 
the space at comfort temperature. In addition, program the 
temperature to this comfort temperature. The thermostat 
activates the heating or cooling at the proper time to reach the 
scheduled temperature at the scheduled time.
NOTE: The setpoint changes gradually to use economical 
stages and avoid overshoot.
For example—the space will be occupied at 8:00 AM and the 
desired temperature is 70°F. Set the OCC 1 period for 8:00 AM 
and 70°F. The thermostat turns on the heat prior to 8:00 AM to 
raise the temperature to 70°F by 8:00 AM.
The thermostat provides an alert that the heating or cooling 
system is coming on before a scheduled time by displaying 
“Recovery” on the screen.
Minimum-Off Timer Compressor Protection
The thermostat has an adjustable Minimum-Off Timer that can 
be set from zero to five minutes (Factory Setting—five 
minutes). The Minimum-Off Timer can be bypassed through 
the Installer System Test or it can be bypassed permanently by 
setting the Minimum-Off Timer to 0 minutes in the Installer 
Setup. The Minimum-Off Timer is activated after the 
compressor turns off:
— If the thermostat is system powered (common wire), the 
Minimum-Off Timer is also activated upon initial startup and 
after power interruptions.
— If there is a call for cooling or heating during the Minimum-
Off Time, the thermostat displays “Wait.”
— When the Minimum Off Timer expires, “Cool On” or “Heat 
On” (heat pumps only)” appears solidly in the display and 
the compressor and fan turn on.
Economizer/TOD Logic (Table 8)
Table 8. Operation of Terminal A.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Temperature 
Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) 
installed; the thermostat controls this function:
1. Choose correct heat pump application in ISU 0170.
2. Choose Outdoor Temperature Sensor for Heat Pump 
Temperature Lockouts Option in ISU 0340.
3. Choose appropriate Balance Point Temperature in 
ISU 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR 
TEMPERATURE)
When the outdoor temperature is above the selected Balance 
Point Temperature (ISU 0350), only the compressor operates 
and the fan (G terminal) energizes when the thermostat calls 
for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR 
TEMPERATURE)
When the outdoor temperature is below the selected Balance 
Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary 
heat) operates and the fan (G terminal) does not energize 
when the thermostat calls for heat.
Heat Pump with Auxiliary (Backup) Heat and Outdoor 
Temperature Sensor
1. Choose correct heat pump application in ISU 0170.
2. Choose Outdoor Temperature Sensor for Control 
Option in ISU 0340.
3. Choose Compressor Lockout Temperature in 
ISU 0350.
4. Choose Auxiliary Lockout Temperature in ISU 0360.
Effective 
Occupancy
Call for 
Cool
Terminal A
Economizer
TOD
Occupied
Energized
Energized
Unoccupied Yes
Energized
De-energized
No
De-energized
De-energized
Override
Energized
Energized