Honeywell TB7220 User Manual

Page of 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
63-2635—03
20
NOTE: There is a 5°F deadband between Compressor and 
Auxiliary Heat lockout temperatures
Operation in Heat Mode
When the outdoor temperature is:
— Below Compressor Lockout Temperature: only Auxiliary 
Heat operates.
— Above Auxiliary Lockout Temperature: only the Compressor 
operates.
— Between the two temperatures: both the Compressor and 
Auxiliary Heat operate.
Fig. 41. Heat Pump Operation with Lockout Temperatures 
Set.
Operating Sequence
The thermostat energizes specific terminal(s), depending on 
the demand for heating, cooling or fan. The thermostat screen 
shows the time, inside temperature, system and fan selections. 
Additional indicators are shown when the heating, cooling or 
fan is energized. See Tables 9 and 10 for specification 
information.
Table 9. Sequence of Operation for Conventional Systems.
a
If Installer Setup System type is set to two stages of cooling.
b
G energizes only if Installer Setup 0180 is set to Electric.
c
If Installer Setup System type is set to two stages of heating.
Table 10. Sequence of Operation for Heat Pump Systems.
a
Configure O/B in Installer Setup. Based on last piece of 
equipment called (cooling = O; heating = B).
b
If Installer Setup System Type is set to 3Heat/2Cool Heat 
Pump with Auxiliary Heat.
c
If Installer Setup System Type is set to 2Heat/1Cool Heat 
Pump with Auxiliary Heat.
d
This terminal does not energize if Installer Setup System type 
is set to 2 Heat/2 Cool Heat Pump with no Auxiliary Heat.
Second Stage Heat and Cool Control
While maintaining setpoint, several factors affect when 2nd 
stage energizes such as load conditions, environmental 
conditions, P+I control, and home insulation. The second stage 
energizes when the thermostat senses 1st stage is running at 
90% capacity. This operation is droopless control.
Temperature Sensor Operation and Checkout
Allow outdoor or indoor temperature sensor to absorb the air 
for a minimum of five minutes before taking a reading. See the 
Sensor instructions for more information.
NOTE: The C7089U, C7189U, and T7770A Temperature 
Sensors are calibrated at the factory and cannot 
be recalibrated in the field.
C7089U Outdoor Temperature Sensor
Operation
When installed with Thermostat ISU 0340 set to 1 or 2, the 
thermostat can display outside temperature.
Checkout
Allow C7089U Outdoor Sensor to absorb outdoor air for a 
minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]) measure the 
temperature at the sensor location, allowing time for the 
thermometer to stabilize before reading.
System 
Setting
Fan 
Setting Call for Action
Energize 
Terminals
Screen 
Message
Off
Auto
Cool
Auto
Cool
 or Auto
Auto
Stage 1 
Cooling
Y, G
Cool On
Cool
 or Auto
Auto
Stages 1 and 2 
Cooling
Y, Y2
a
, G
Cool On
Heat
Auto
Heat
 or Auto
Auto
Stage 1 
Heating
W, G
b
Heat On
Heat
 or Auto
Auto
Stages 1 and 2 
Heating
W, W2
c
, G
b
Heat On
35
M19950
COMPRESSOR
LOCKOUT
TEMPERATURE
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR ONLY
BOTH COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
50
OUTDOOR TEMPERATURE
System 
Setting
Fan 
Setting Call for Action
Energize 
Terminals
Screen 
Message
Off
Auto
O/B
a
Cool
Cool
 or Auto
Auto
Stage 1 Cooling
Y, G, O/B
a
Cool On
Stages 1 and 2 
Cooling
Y, Y2
b
, G, 
O/B
a
Heat Auto
None
O/B
a
Heat
 or Auto
Auto
Stage 1 Heating
Y, G, O/B
a
Heat On
Stages 1 and 2 
Heating
Y, W1
c
, G, 
O/B
a
Auxiliary 
Heat On
Stages 1, 2 and 3 
Heating
Y, Y2
b
W1
d
, G, 
O/B
a