TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
62-0273—05
2
CAUTION
Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect power supply before installation.
Select Thermostat Location
Select a location for the thermostat about 5 ft (1.5m) 
above the floor in an area with good air circulation at 
average temperature. See Fig. 1.
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall 
behind the thermostat.
Separate Wallplate from Thermostat
1. Separate the wallplate from the thermostat. See 
Fig. 2. Separate wallplate from thermostat.
Install Wallplate (See Fig. 3)
Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow 
pointing up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two 
3/16 in. holes in the wall (if drywall) as marked. For 
firmer material such as plaster, drill two 7/32 in. 
holes. Tap the wall anchors (provided) into the 
drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate 
and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors 
and tighten.
Fig. 3. Install wallplate.
WIRING
IMPORTANT
— All wiring must agree with applicable codes, 
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is 
not required.
NOTES:
Sensor wires must have a cable separate 
from the thermostat control cable.
Refer to Table 2 for terminal designation 
descriptions.
See Fig. 6 through 17 for wiring diagrams for 
specific equipment applications.
1. Select set of terminal identifications that correspond 
to your system type (conventional or heat pump). 
(See Fig. 4).
Fig. 4. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and tighten 
each screw terminal.
4. Push excess wire back into the wall opening and 
restrict wires to the shaded area. See Fig. 5.
5. Plug the wall opening with nonflammable insulation 
to prevent drafts from affecting the thermostat.
5 FEET
[1.5 METERS]
YES
NO
M22258
NO
NO
THERMOSTAT
WIRE HOLE
M22267
WALLPLATE
M22268
DRILLED  
HOLES (2)
WALL
ANCHORS (2)
MOUNTING
SCREWS (2)
WALLPLATE
M27415
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
SCREW  
TERMINALS