TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
62-0273—05
6
PTAC System Wiring
Fig. 16. Typical hookup of PTAC with HI and LO fan 
speeds (1H/1C).
Fig. 17. Typical hookup of PTAC with HI and LO fan 
speeds (2H/1C).
Sensor Wiring for Temperature Averaging
Fig. 18. Wiring four TR21 (20K ohm) Sensors.
Fig. 19. Wiring two TR21-A (10K ohm) Sensors to 
provide a temperature averaging network.
Fig. 20. Wiring two TR21 (20K ohm) Sensors and one 
TR21-A (10K ohm) Sensor to provide a temperature 
averaging network
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
COMPRESSOR CONTACTOR 
M27426
CHANGEOVER VALVE 
1
2
3
4
5
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS 
OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE 
INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. 
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT 
CABLE.
L1  
(HOT) 
L2 
24 VAC 
5
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
HIGH FAN RELAY
COMPRESSOR CONTACTOR
M27427
CHANGEOVER VALVE
1
2
3
4
5
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS 
OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" 
IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. 
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT 
CABLE.
L1  
(HOT) 
L2 
24 VAC 
AUXILIARY HEAT RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
5
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
HIGH FAN RELAY
M27481
S1 S2 
T T 
SUBBASE 
TR21
T T 
TR21
T T 
TR21
T T 
TR21
M27482
S1
S2
SUBBASE 
TR21-A
T4 T3 
TR21-A
T4 T3 
1
1
1
THE TR21-A IS A 10K OHM SENSOR.
M27483
T4 
T3
TR21-A
1
THE TR21-A IS A 10K OHM SENSOR.
S1
S2
T
T
SUBBASE
TR21
T
T
TR21