Siemens RDF600 Leaflet

Page of 2
CE1B3176.3en / 2012-08-29 
Subject to change 
Siemens Building Technologies  
Button lock  
   
 
 
 
 
Press operating mode button   for 3 seconds to lock or unlock the buttons if 
manual button lock is configured (parameter P14 = 2).   
The thermostat automatically locks the buttons 30 seconds after the last 
adjustment if "Auto lock" is configured (P14 = 1).  
 
The key symbol 
 indicates locked buttons.  
Reminder to clean filters 
External faults 
Commissioning (by qualified HVAC installer) 
 
To adapt the thermostat to your system and optimize the control performance, a number 
of control parameters can be adjusted. This can also be made during operation without 
opening the thermostat. 
Control sequence 
Recalibrating the sensor 
Note: Economy mode 
 
 
 
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for 
cooling. Use parameters P11 and P12 to adjust the values. 
Important:  You can set these setpoints to OFF; the thermostat then is 
inactive, i.e. no protective heating or cooling function.  Risk of frost! 
Control parameters 
Proceed as follows to change the most important control parameters: 
(Your HVAC installer can set additional parameters) 
 
 
+ / - 
 
+ / - 
 
 
 
+ / - 
 
+ / - 
1.  Set the thermostat to Protection   
2.  Press - and + simultaneously for a minimum of 4 seconds.  
Release them and, within 2 seconds, press + again until "P01" is displayed. 
3.  Repeatedly press the + or  button to select the required parameter. 
P01
P02
P08
P13
+
-
+
-
-
+
3057z03
P14
-
+
-
P12
+
-
 
4.  Press + and  simultaneously, the current value of the selected parameter starts to flash, allowing you to change 
the value by repeatedly pressing + or 
5.  The next parameter is displayed when you press + and  again simultaneously. 
6.  Repeat steps 3 to 5 to display and change additional parameters. 
7.  15 seconds after the last display or setting, all changes are saved and the thermostat will leave parameter entry 
mode. 
 
Para-
meter 
Description 
Factory setting 
Setting range  
 
P01 Control 
sequence 
 
2-pipe:  [0…3] 
1 (Cooling only)  
 
4-pipe:  [2…4] 
4 (Heating & Cooling) 
0 = Heating only 
1 = Cooling only 
2 = Manual H or C 
3 = Auto Changeover 
4 = Heating & cooling 
 
P02 
Mode selection by user via operating mode button 
1 (Protection, 
Comfort) 
1 = Protection, Comfort, 
2 = Protection, Comfort,  
 Economy 
 
P04 
Selection of °C or °F 
0 (°C) 
0 = °C  
1 = °F 
 
P05 Sensor 
calibration 
0.0 K 
– 3 ... +3 K 
 
P06 
Standard temperature display 
0 (Room temp.) 
0 = Room temperature 
1 = Setpoint 
 
P07 
Additional user information 
0 (no display) 
0 = no display 
1 = Temp in °C / °F 
 
P08 
Comfort basic setpoint 
21 °C 
5 ... 40 °C 
 
P09 
Minimum setpoint limitation in Comfort 
(Wmin
Comf
) 5 °C 
5 ... 40 °C 
 
P10 
Maximum setpoint limitation in Comfort 
(Wmax
Comf
) 35 °C 
5 ... 40 °C 
 
P11 
Setpoint of heating in Economy mode  
(Wheat
Eco
) 15 °C 
OFF, 5 °C…Wcool
Eco
 
 
P12 
Setpoint of cooling in Economy mode 
(Wcool
Eco
) 30 °C 
OFF, Wheat
Eco
…40°C  
P13 
Electric heater in cooling mode 
ON 
OFF = Disabled  
ON =  Enabled 
 
P14 
Button lock 
(Press operating mode button   for 3 seconds to lock or 
unlock the buttons)
 
0 (Disabled) 
0 = Disabled 
1 = Auto lock 
2 = Manual lock 
 
 
The control parameters displayed depend on the DIP switch settings made
 
  Please record all changes you make!  
(All temperature settings can be made in increments of 0.5 K) 
    FIL  This message reminds you to clean the filter on your HVAC equipment.   
It will appear after  __________ "fan operating hours" and disappear when 
the thermostat is set to Protection ( ).   
This reminder must be configured by your HVAC installer. 
 
    AL1 
    AL2 
This alarm message tells you an external alarm has occurred: 
    AL1 : ______________________    
    AL2 : ______________________ 
The alarms are configured by your HVAC installer 
 
The thermostat can be used in systems either for heating only or cooling 
only
manually selection of heating or cooling, or automatic heating / cooling 
changeover
. Depending on the selected application, the relevant modes are 
available and can be adjusted by commissioning parameter P01 if needed. 
 
 
The factory setting for 2-pipe application is "Cooling only", and for 4 pipe 
application "Heating and Cooling" 
 
If the room temperature displayed by the thermostat does not agree with the 
temperature effectively measured (after min 1 hour of operation), the tem-
perature sensor can be recalibrated. With parameter P05 the temperature can 
be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.