WEBVISION™
95-7769—01
20
• Save – Any change done in the UI is automatically saved 
locally in the Web UI. To save the modified configuration in 
the WebVision click Save. To write the saved data onto 
device, use the Device Download option.
Set Points
NOTE: The Setpoints tab appears only for the supported 
devices.
To set the setpoint for a device:
On the left corner of the screen, WebVision is listed. Expand 
WebVision to view all the devices associated with it.
1. Select a device from the list of devices in WebVision. 
Click the corresponding link to view the properties of 
that device.
2. Click the SetPoints tab. The SetPoints page appears.
3. Select the following parameters:
• Permanent Set points:
• Occupied: Specify the Cooling SetPoints and 
the Heating SetPoints.
• Standby: Specify the Cooling SetPoints and the 
Heating SetPoints.
• Unoccupied: Specify the Cooling SetPoints and 
the Heating SetPoints.
• Select the override duration, if any, using the 
Override Duration for Setpoint and 
Occupancy State drop-down list.
• Fan and System Switch:
• System Switch: Specify the system switch 
mode: HeatAutoCool, or Off.
• Fan Switch: Specify the fan switch mode: On or 
Auto.
4. Click Save to save the settings.
Sensor Calibration
NOTE: The Sensor Calibration tab appears only for the 
supported devices that have analog inputs.
This is a process of configuring the controller to correct error 
in the value provided by the sensor. 
To calibrate a sensor:
On the left corner of the screen, WebVision is listed. Expand 
WebVision to view all the devices associated with it.
1. Select a device from the list of devices in WebVision. 
Click the corresponding link to view the properties of 
that device.
2. Click the Sensor Calibration tab. The Sensor 
Calibration page appears. All the sensors associated 
with the selected device are listed in the Sensor Name 
list. The Actual Reading column lists the actual value 
measured by the sensor. 
3. Specify the correct value that the controller is supposed 
to measure in Calibrated Value column. The difference 
between the two values is displayed in Calibrated 
offset column. The controller adds the calibrated offset 
value to the measured value to correct the error. 
4. Click Save to save the settings.
Balancing
This process helps the VAV devices to calibrate their flow 
sensors for better air flow control.
NOTE: To perform balancing ensure that the VAV device is 
online.
To view the Balancing page:
1. Click the Balancing tab. The Balancing page appears.
2. The following information is displayed in tabular format:
• Device Name: Name of the device
• Channel Name: Name of the channel on which the 
device exists.
• Balanced On: Balancing status. It can be Balanced 
or Not Balanced.
NOTE: Use Filters to quickly search the required device.
Use one of the following filter options to search for the 
required device:
• Device Name
• Device Type
• Is Balanced
NOTE: To quickly search the devices, type the first letter of 
the required filter criteria in the Keyword text box 
and type an asterisk (*). This lists all the names 
starting with the first letter that you have written in the 
Keyword text box.
To view Balancing details:
1. Click the Balancing tab to display the Balancing page.
2. Select a device from the list and click Balance to 
display the balancing details of the selected device.
3. View/Edit the following details:
• Device Name: Name of the VAV device which is 
selected for balancing.
• Damper Position: Displays the position of the 
damper. This field is non-editable. The damper 
position varies to attain stable air flow. 
• Sensed Airflow: Displays the actual air flow that is 
measured by a pressure sensor connected to the 
VAV device. This field is non-editable. 
• Max Airflow Setpoint: This allows you to set the 
maximum airflow setpoint. The field is enabled by 
default. Enter the maximum airflow setpoint value, 
use Change max setpoint to write the maximum 
airflow setpoint to the device. 
• Start Max Balance: Click on this button to balance 
the device for the maximum air flow setpoint. 
• Min Airflow Setpoint: This allows you to set the 
minimum air flow setpoint value which must be less 
than the maximum value. The field is enabled by 
default. It allows you to set the minimum airflow 
setpoint value, use Change min setpoint to write 
the minimum airflow setpoint to the device. 
• Start Min Balance: Click on this button to balance 
the device for the minimum air flow setpoint. 
• Zero Airflow Setpoint: By default 0 is the setpoint 
value and you cannot edit this field. 
• Start Zero Balance: Click on this button to balance 
the device for the zero air flow setpoint.
4. Click Save to save the settings.