Honeywell 95-7769-01 User Manual

Page of 176
WEBVISION™
79
95-7769—01
UV Zone Options
Use Table 58 to configure the Unit Ventilator Zone Options to 
set the heating and cooling setpoints.
Purpose
Enter all outputs, including optional outputs, to be controlled 
by the Unit Ventilator Controller.
Mode
Configuration can be performed with the wizard Off-line or 
On-line. 
Procedure
1. Click the Zone Options button on the left pane to open 
the Zone Options Configuration page. 
2. Enter information into available fields. 
3. Click Commit to save the settings or Reset to revert to 
the last saved settings. 
4. Click Next to display the Miscellaneous Parameters 
Configuration page or Back to display the H/C Stage 
Parameters Configuration page. 
UV Zone Options fields
UV Miscellaneous Settings
Use Table 59 to configure the miscellaneous Unit Ventilator 
application settings.
Purpose
Enter all outputs, including optional outputs, to be controlled 
by the Unit Ventilator Controller.
Mode
Configuration can be performed with the wizard Off-line or 
On-line. 
Procedure
1. Click the Miscellaneous button on the left pane to open 
the Miscellaneous Parameters Configuration page. 
2. Enter information into available fields. 
3. Click Commit to save the settings or Reset to revert to 
the last saved settings. 
4. Click Next to display the PID Configuration page or 
Back to display the Zone Options Configuration 
page. 
UV Miscellaneous settings
Table 58. Unit Ventilator Zone Options.
Name
Definition
Cooling Occupied 
Setpoint
Enter Occupied cooling setpoint; 
range: 50 to 95 °F (10 to 35 °C).
Cooling Standby 
Setpoint
Enter Standby cooling setpoint; 
range: 50 to 90 °F (10 to 32 °C).
Cooling 
Unoccupied 
Setpoint
Enter Unoccupied cooling setpoint; 
range: 50 to 90 °F (10 to 32 °C).
Heating Occupied 
Setpoint
Enter Occupied heating setpoint; 
range: 50 to 90 °F (10 to 32 °C).
Heating Standby 
Setpoint
Enter Standby heating setpoint; 
range: 50 to 90 °F (10 to 32 °C).
Heating 
Unoccupied 
Setpoint
Enter Unoccupied heating setpoint; 
range: 50 to 90 °F (10 to 32 °C).
Use Wall Module 
Setpoint
Select usage of setpoint adjustment 
potentiometer on a connected Wall 
Module. 
This field is active if you selected a 
Sensor_Setpoint type in the Wall Module 
field on the Input tab.
Min. Limit 
Setpoint
Provides a lower limit on the allowed 
settings of the Wall Module’s setpoint 
knob. 
Enabled if Use Wall Module Setpoint is 
Yes. Values range from 55 to 85 °F when 
the setpoint knob type is absolute and 
range for relative setpoint knob type is –9 
to 9 DDf.
Max. Limit 
Setpoint
Provides an upper limit on the allowed 
settings of the Wall Module’s setpoint 
knob. 
Enabled if Use Wall Module Setpoint is 
Yes. Values range from 55 to 85 °F when 
the setpoint knob type is absolute and 
range for relative setpoint knob type is –9 
to 9 DDf.
Table 59. Unit Ventilator Miscellaneous Settings.
Name
Definition
DLC Setpoint 
Bump
Upon receipt of a DLC_Shed signal over 
the LonWorks-Bus network, the current 
operating setpoint value is bumped up/
down (for cool/heat modes) by this 
amount. Select a value from 0 through 10.
Override Type
Specify the type of Bypass override 
functions that are available from the Wall 
Module's Override button. You can select 
one of the following options:
• None 
• Normal 
• ByPassOnly 
NOTE: No Continuous Unoccupied 
allowed from the Wall Module's 
Override button.
Table 58. Unit Ventilator Zone Options. (Continued)
Name
Definition