Hearth & Home Technologies 21M-ACC User Manual

Page of 44
Page  16
7039-131F
September 1, 2008
R
2100 Millennium Wood Stove  (ACC)
Chimney Height / Rise and Run
This product was designed for and tested on a 6 inch (152mm) 
chimney, 14 to 16 feet (420-480cm) high, (includes stove 
height) measured from the base of the appliance.  The further 
your stack height or diameter varies from this configuration, 
the possibility of performance problems exists. 
Chimney height may need to be increased by 2 - % per 
each 1000 feet above sea level.  It is not recommended to 
use offsets or elbows at altitudes above 4000 feet above sea 
level or when there are other factors that affect flue draft.
C. Installing Chimney Components
Chimney Connector
Single wall connector or stove pipe.  
This must be at least 24 gauge mild steel or 26 gauge blue 
steel.  The sections must be attached to the appliance and to 
each other with the crimped (male) end pointing toward the 
stove.  All joints, including the connection at the flue collar, 
should be secured with  sheet metal screws.  Make sure 
to follow the minimum clearances to combustibles.   Where 
passage through the wall, or partition of combustible con-
struction is desired in Canada, the installation shall conform 
to CAN/CSA-B65.
Factory-built listed chimney connector (vented).
A listed connector (vented) must be used when installing this 
unit in a mobile home.  The listed connectors must conform 
to each other to ensure a proper fit and seal.
Flue Gas 
Direction 
Crimped 
End 
Toward 
Stove 
Secure pipe sections with a 
minimum of 3 screws 
Figure 16.2   Chimney Connector  (Stove Pipe)
WARNING
•  Do NOT connect this unit to a chimney flue 
servicing another appliance.
•  Do NOT connect to any air distribution duct 
or system.
May allow flue gases to enter the house.
Asphyxiation Risk.
Improper installation, adjustment, alteration, service or 
maintenance can cause injury or property damage. Refer 
to the owner’s information manual provided with this appli-
ance. For assistance or additional information consult a 
qualified installer, service agency or your dealer.
WARNING
Fire Risk.
Inspection of Chimney:
•  Chimney must be in good condition.
•  Meets minimum standard of NFPA 211
•  Factory-built chimney must be 6 inch 
(152mm) UL10 HT.
WARNING
WARNING
ONLY use connector:
•  Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
•  Attic or roof space
•  Closet or similar concealed space
•  Floor or ceiling
Maintain minimum clearances to combustibles
Fire Risk.
Follow Chimney Connector Manufacturer’s 
Instructions for Proper Installation.
Chimney Flue 
Liner 
Fireclay 
Liner or 
Equivalent 
Masonry Chimney 
Constructed to NFPA 211 
Wall Spacer 
Wall Band 
Trim Collar 
Chimney 
 Connector 
1 inch (25mm) Air 
Space to Chimney 
Section 
Min. Clearance 
2 inch (51mm) 
Min. Chimney Clearance to 
Wall Spacer and 
Combustibles - 2 inch (51mm) 
Chimney Section 
Figure 16.1
Solid Pack Chimney with Metal Supports as a 
Thimble (Cont’d)