2100 Millennium Wood Stove (ACC)
R
D.  Chimney Termination Requirements
Follow manufacturer’s instructions for clearance, securing 
flashing and terminating the chimney.
   
Must have an approved and listed cap
 
 
Must not be located where it will become plugged by 
snow or other material
 
•  Must terminate at least  feet (91cm) above the roof 
and at least 2 feet (61cm) above any portion of the 
roof within 10 feet (05cm).
 
•  Must  be  located  away  from  trees  or  other  struc-
tures
These are safety requirements and are not meant to assure proper flue draft.
Figure 17.1
E.  2-10-3 Rule
Figure 17.2
NOTE:
•  Chimney performance may vary.
•  Trees, buildings, roof lines and wind conditions affect 
performance.
•  Chimney height may need adjustment if smoking or 
overdraft occurs.
3 ft.  (91cm)
Minimum
Less than 10 ft. (305cm) 
2 ft. (61cm)  
3 ft. (91cm)  
Minimum 
10 ft. (305cm) To Nearest Roofline 
2 ft. (61cm) 
Pitched Roof 
10 ft. (305cm) or more
3 ft.  (91cm) Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Wall or Parapet
Flat Roof