Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1095
M/T-ANL (Maintenance/Test Analog Port) 
9
M/T-ANL (Maintenance/Test Analog 
Port)
The Maintenance/Test Analog Port is port number 1 on the TN771 
Maintenance/Test circuit pack. This port is used by the Automatic Transmission 
Measurement System (ATMS) as an Originating Test Line (OTL) or Terminating 
Test Line (TTL) for test calls over analog trunks. For more details, see ‘‘Automatic 
Trunk Transmission System’’ i
Chapter 6, ‘‘Additional Maintenance Procedures’’
Figure 9-65
 shows a typical ATMS configuration.
M/T-ANL maintenance ensures that the analog trunk’s testing function is 
operating correctly. An alarm against M/T-ANL can reduce service, but it will not 
block it. To accurately measure performance and health of analog trunks, the 
TN771 should be replaced when a new circuit pack is available.
Figure 9-65.
ATMS Tie Trunk Test Call
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to Run
1
1.
UU is the universal cabinet number (1 for PPN, 2 - 44 for EPNs). C is the carrier designation (A, 
B, C, D, or E). 
SS is the number of the slot in which the circuit pack resides (01 to 21). pp is the 
two digit port number (01, 02, ...).
Full Name of MO
M/T-ANL
Minor
test port UUCSSpp l 
Maintenance/Test Analog Port
M/T-ANL
Warning
release port UUCSSpp 
Maintenance/Test Analog Port
Tie
Trunk
Facilities
Originating
Test Line
(OTL)
TN771
TDM Bus
Terminating
Test Line
(TTL)
TN771
TDM Bus
PBX originating
the test call
PBX terminating
the test call
Tie Trunk
Circuit Pack
Tie Trunk
Circuit Pack