STRAT-3 (Stratum 3 Clock) 
9
STRAT-3 (Stratum 3 Clock)
The 
Digital Synchronization Network Plan (PUB 60110) specifies a hierarchy of 
synchronization nodes consisting of strata 1 to 4, where the sole Stratum 1 clock 
in the network is the most accurate. The Release 5r system supports both 
Stratum 3 and Stratum 4 operations. Refer to “SYNC (Synchronization)” for 
details on Stratum 4 operation.
A Stratum 3 clock derives its timing from two DS1 references connected to a 
Stratum 3 or better source. The Stratum 3 clock provides a holdover of at least 24 
hours should both DS1 references fail. (After 24 hours, the Stratum 3 clock still 
provides service but its accuracy may be degraded). The 
Digital Synchronization 
Network Plan (PUB 60110) requires that the Stratum 3 clock have duplicated 
components.
The Stratum 3 clock can be configured with only one DS1 input if one of the 
Clock Input cards is removed. Also, the Stratum 3 clock can free run (use its 
internal clock without using DS1 inputs, if both Clock Input cards are removed).
The recognition of the Stratum 3 clock itself as well as its alarm signals, is 
supported only by the TN780 Tone-Clock circuit pack. The TN780 Tone-Clock 
circuit pack is also backwards-compatible with the TN768 Tone-Clock circuit 
pack. The Stratum 3 clock may be connected to the PPN if the TN780 Tone-Clock 
circuit pack(s) is present in that port network. The Stratum 3 clock should never 
be connected to an EPN.
The only operation that software can perform is a query of the alarm leads. The 
only recovery action that can be performed on a catastrophic failure of the 
Stratum 3 clock is using the local oscillator on the active TN780 Tone-Clock 
circuit pack. Neither software nor the TN780 Tone-Clock circuit pack can request 
additional information about the health of the Stratum 3 clock other than the 
information provided by the alarm leads. Furthermore, neither the software nor 
the TN780 Tone-Clock circuit pack can request that the external clock switch 
references, change configuration, disable/enable, initialize, and so forth.
In the system, the Stratum 3 clock has been implemented as an external which 
follows the specification in PUB 60110 for Stratum 3. The only external Stratum 3 
clock that is supported is the Telecom Solutions Digital Clock Distributor
 for 
Customer Premise Timing (DCD-CPT) Stratum 3 clock. 
 shows how 
the Stratum 3 hardware configuration provides clock and alarm signals to the 
TN780 Tone-Clock circuit pack(s). The reference DS1 facilities connect directly to 
the Stratum 3 clock for timing purposes, but the DS1 data may be routed into the 
MO Name (in 
Alarm Log)
Alarm Level
Initial Command to Run 
Full Name of MO
STRAT-3
MAJOR
test synchronization
Stratum 3 Clock
STRAT-3
MINOR
test synchronization
Stratum 3 Clock